Operation, Setup, Metering parameters – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 45: Commands, Related functions
![background image](/manuals/579043/45/background.png)
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
45
PowerMonitor 1000 Unit Features Chapter 2
Operation
Each time status input 1 sees an off-to-on transition, the status input 1 scale
factor is added to the status input 1 count. The count continues to increase,
rolling over to zero at a value of 9,999,999,999,999 (10
12
– 1). Status input 2
operates in the same fashion. Status input 2 counter operates whether or not the
input is used for demand EOI synchronization.
Setup
The set-up parameters for pulse totalizing and scaling are in the Advanced Setup
menu and are summarized in this table.
Setup for demand EOI synchronization is described in the
section.
Metering Parameters
•
Status 1 Count x1,000,000 and x1
•
Status 2 Count x1,000,000 and x1
Commands
The following commands may be used to preset or reset the status input counters:
•
Set Status 1 Count
•
Set Status 2 Count
Related Functions
•
Log status input changes
•
Configuration lock
Parameter
Description
Range
Default
User
Setting
Model
TR1
TR2
EM1
EM2
EM3
Status Input 1 Input
Scale
When a status input sees an
off to on transition, the
status input count is
increased by the scale
factor.
1… 1,000,000 1
•
•
•
Status Input 2 Input
Scale
1…
1,000,000
1
•
•
•