PowerMonitor 1000 Data Tables Appendix A

Table 21 - Controller Interface Table Parameters

CSP File No.

N18

CIP Instance

11

Applies to

EM2, EM3 only

No. of Elements

8

No. of Words

8

Data Type

Integer

Data Access

Write

Table 22 - Controller Interface Table

Element

No.

Modbus

Address

Element Name

Default

Value

Range

Description

0

40801

Password

0

0…9999

When writing the complete table this parameter allows the input data to be

accepted. When writing a single parameter the separate password table

should be used. Returns -1 on a read.

1

40802

Controller

Command Word

0

0…1

Bit 0 = When this bit is written to the power monitor it signals the end of the

demand period. The power monitor resets the bit to 0 and sends the end of

demand broadcast to all of the slaves configured for the master/slave

demand system. The power monitor must be configured as a Master for

external demand pulse input.

Bit 1…15 = Reserved

2

40803

Reserved

0

0

Reserved for future use.

3

40804

Reserved

0

0

Reserved for future use.

4

40805

Reserved

0

0

Reserved for future use.

5

40806

Reserved

0

0

Reserved for future use.

6

40807

Reserved

0

0

Reserved for future use.

7

40808

Reserved

0

0

Reserved for future use.