PowerMonitor 1000 Data Tables Appendix A
Table 21 - Controller Interface Table Parameters
CSP File No.
N18
CIP Instance
11
Applies to
EM2, EM3 only
No. of Elements
8
No. of Words
8
Data Type
Integer
Data Access
Write
Table 22 - Controller Interface Table
Element
No.
Modbus
Address
Element Name
Default
Value
Range
Description
0
40801
Password
0
0…9999
When writing the complete table this parameter allows the input data to be
accepted. When writing a single parameter the separate password table
should be used. Returns -1 on a read.
1
40802
Controller
Command Word
0
0…1
Bit 0 = When this bit is written to the power monitor it signals the end of the
demand period. The power monitor resets the bit to 0 and sends the end of
demand broadcast to all of the slaves configured for the master/slave
demand system. The power monitor must be configured as a Master for
external demand pulse input.
Bit 1…15 = Reserved
2
40803
Reserved
0
0
Reserved for future use.
3
40804
Reserved
0
0
Reserved for future use.
4
40805
Reserved
0
0
Reserved for future use.
5
40806
Reserved
0
0
Reserved for future use.
6
40807
Reserved
0
0
Reserved for future use.
7
40808
Reserved
0
0
Reserved for future use.