Commands, Related functions, Min/max log – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 40: Logged parameters, Results
![background image](/manuals/579043/40/background.png)
40
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Chapter 2 PowerMonitor 1000 Unit Features
Commands
•
Clear energy log
Related Functions
•
Energy metering, Demand metering
•
Configuration lock
Min/Max Log
The power monitor records time-stamped minimum and maximum values for all
real-time metering data (except for energy data).
This feature applies to catalog numbers 1408-TR1, 1408-TR2, and 1408-EM3.
Logged Parameters
The min/max log contains a record for each of the metering parameters listed
below along with a date/time stamp corresponding to the minimum and
maximum value recorded.
Results
Min/max log records can be accessed only via communication.
Metering Parameter
TR1
TR2
EM3
L1, L2, L3 and Average Current
•
•
•
L1-N, L2-N, L3-N and Average L-N Voltage
•
•
•
L1-L2, L2-L3, L3-L1 and Average L-L Voltage
•
•
•
Frequency
•
•
•
Percent Current Unbalance
•
•
•
Percent Voltage Unbalance
•
•
•
L1, L2, L3 and Total True Power Factor
•
•
L1, L2, L3 and Total Real Power, kW
•
•
L1, L2, L3 and Total Reactive Power, kVAR
•
•
L1, L2, L3 and Total Apparent Power, kVA
•
•
Real Power Demand, kW
•
Reactive Power Demand, kVAR
•
Apparent Power Demand, kVA
•
Demand PF, percent
•