PowerMonitor 1000 Data Tables Appendix A
Table 6 - Advanced Configuration Parameters
CSP File No.
F11
CIP Instance
4
No. of Elements
22
No. of Words
44
Data Type
Float
Data Access
Read/Write
Table 7 - Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0
40101-2
Password
0
0…9999
•
•
•
•
•
When writing the complete table this
parameter allows the input data to be
accepted. When writing a single parameter the
separate password table should be used.
Returns -1 on a read.
1
40103-4
New Password 0
0…9999
•
•
•
•
•
This becomes the new password when the
proper the configuration password entry has
been made and this parameter is greater than (-
1).
2
40105-5
Metering
Result
Averaging
1
0…1
•
•
•
•
•
The metering results for volts, amps, power and
frequency is averaged over 8 cycles of data to
provide a steady output reading.
0 = Off
1 = On
3
40107-8
Log Status
Input Changes
0
0…1
•
•
•
•
•
0 = Disable recording of status input changes
into the status log.
1 = Enable recording of status input changes
into the status log.
4
40109-10
Use Daylight
Savings
Correction
0
0…1
•
•
•
•
•
0 = Disable Daylight Savings
1 = Enable Daylight Savings
5
40111-12
Daylight
Savings
Month/Week/
Day Start
030201
March, 2nd,
Sunday
10101…
120507
•
•
•
•
•
This is the day that the power monitor will add
an hour to the time. This feature also looks at
Ethernet SNTP offset and corrects for Daylight
Savings.
Example: 040107 = April/1st week/Sunday
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
6
40113-14
Hour of Day
Start
2
0…23
•
•
•
•
•
The hour of day the daylight savings
adjustment should be made to add an hour.