Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 102
![background image](/manuals/579043/102/background.png)
102
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 44 - Min/Max Log Results Parameters
CSP File No.
F29
CIP Instance
22
No. of Elements
11
No. of Words
22
Data Type
Float
Data Access
Read
Table 45 - Min/Max Log Results
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
0
31001-2
Parameter Being
Returned
1…35
•
•
•
Indicates the Parameter Number (See Min/
Max Parameter List).
1
31003-4
MIN Value
+/-
0.000…9,999,
999
•
•
•
The minimum value recorded for parameter
being returned since the last clear
command.
2
31005-6
MAX Value
+/-
0.000…9,999,
999
•
•
•
The maximum value recorded for
parameter being returned since the last
clear command.
3
31007-8
Timestamp Year of MIN
•
•
•
The year when the MIN value was
recorded.
4
31009-10
Timestamp Month/Day
of MIN
•
•
•
The month and day when the MIN value
was recorded.
5
31011-12
Timestamp Hour/Minute
of MIN
•
•
•
The hour and minute when the MIN value
was recorded.
6
31013-14
Timestamp Seconds/
Hundredths of MIN
•
•
•
The seconds and hundredths when the
MIN value was recorded.
7
31015-16
Timestamp Year of MAX
•
•
•
The year when the MAX value was
recorded.
8
31017-18
Timestamp Month/Day
of MAX
•
•
•
The month and day when the MAX value
was recorded.
9
31019-20
Timestamp Hour/Minute
of MAX
•
•
•
The hour and minute when the MAX value
was recorded.
10
31021-22
Timestamp Seconds/
Hundredths of MAX
•
•
•
The seconds and hundredths when the
MAX value was recorded.