Explicit Messaging Chapter 5
Log Data Table Methodology
The log data tables only hold one record instance for a specific log. Successive
reads of the data table return a successive record instance for that log. By writing
to specific configuration elements in the Log Request Table data table, you can
configure the log to return in a forward or reverse direction. You can also
configure the log to return a specific record for all logs except the Unit Status
Log, and Energy Log.
Refer to Log Request Table on page 85
for more information.
Example 1: Read the 5
th
Log Record in the Load Factor Log
This example explains how to configure the Log Request Table to read the 5
th
log
record in the Load Factor Log.
1. Create a write message to write the following values to the Log Request
Table.
2. Create a read message to read the values in the Load Factor Log table.
Element
Item Name
Value
0
Selected Log
4
1
Chronology of Auto Return Data
0
2
Mix/Max Record to be Returned
0
3
Number of Unit Status Records
0
4
Number of Energy Log Records
0
5
Number of Time of Use Log Records
0
6
Number of Load Factor Log Records
0
7
Load Factor or TOU Record to be Returned
5