Explicit Messaging Chapter 5

Log Data Table Methodology

The log data tables only hold one record instance for a specific log. Successive

reads of the data table return a successive record instance for that log. By writing

to specific configuration elements in the Log Request Table data table, you can

configure the log to return in a forward or reverse direction. You can also

configure the log to return a specific record for all logs except the Unit Status

Log, and Energy Log.

Refer to Log Request Table on page 85

for more information.

Example 1: Read the 5

th

Log Record in the Load Factor Log

This example explains how to configure the Log Request Table to read the 5

th

log

record in the Load Factor Log.

1. Create a write message to write the following values to the Log Request

Table.

2. Create a read message to read the values in the Load Factor Log table.

Element

Item Name

Value

0

Selected Log

4

1

Chronology of Auto Return Data

0

2

Mix/Max Record to be Returned

0

3

Number of Unit Status Records

0

4

Number of Energy Log Records

0

5

Number of Time of Use Log Records

0

6

Number of Load Factor Log Records

0

7

Load Factor or TOU Record to be Returned

5