Appendix A PowerMonitor 1000 Data Tables
7
40115-16
Return from
Daylight
Savings
Month/Week/
Day
110101
November,
1st, Sunday
10101…
120507
•
•
•
•
•
This is the day that the power monitor will
subtract an hour from the time. This feature
also looks at Ethernet SNTP offset and corrects
for the return from Daylight Savings.
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
8
40117-18
Hour of Day
End
2
0…23
•
•
•
•
•
The hour of day the daylight savings
adjustment should be made to subtract an hour.
9
40119-20
KYZ Solid
State Output
Parameter
0
0…5
•
•
•
The parameter selected will pulse the KYZ
output at a rate that equals the parameter
value divided by KYZ scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd (EM2 and EM3 Only)
4 = VARh Rev (EM2 and EM3 Only)
5 = Vah (EM2 and EM3 Only)
10
40121-22
KYZ Solid
State Output
Scale
1,000
1…
100,000
•
•
•
The KYZ output parameter divided by the scale
is the output pulse rate. Example: Wh is
selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.
11
40123-24
KYZ Pulse
Duration
Setting
250 ms
0 or
50…1000
•
•
•
Set as 50…1000 to indicate the duration of the
pulse in milliseconds, or set to 0 for KYZ-style
transition output. (Toggle)
The value for delay is rounded off to the
nearest 10ms internally during this function.
12
40125-26
Status Input 1
Input Scale
1
1…
1,000,000
•
•
•
When a status pulse is received the count is
increased by the scale factor. Input pulse *
input scale added to total status count.
13
40127-28
Status Input 2
Input Scale
1
1…
1,000,000
•
•
•
When a status pulse is received the count is
increased by the scale factor. Input pulse *
input scale added to total status count.
14
40129-30
Demand
Source
0
0…3
•
•
When item Demand Broadcast Master Select
of the ethernet table is set to master a
selection of 0 through 2 sets the type of master
input. In this case item 3 is ignored. When the
Demand Broadcast Master Select of the
ethernet table is set to slave then any of these
inputs can set the end of the demand period.
Selections of 0 through 2 can be selected for
RS485 units.
0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast
Selection 3 can only be programmed when the
Ethernet option is installed.
Table 7 - Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR
1
TR
2
EM
1
EM
2
EM
3
Description