Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

Table 53 - Time of Use Log Results - Apparent Energy and Demand Parameters

CSP File No.

F33

CIP Instance

26

No. of Elements

12

No. of Words

24

Data Type

Float

Data Access

Read

Table 54 - Time of Use Log Results - Apparent Energy and Demand

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

31401-2

Record Number

1…13

The record number of the log. Record 0 is always

the current record before being logged.

1

31403-4

Time Stamp Start

Date (yy/mm/dd)

-

The Date this record was started.

2

31405-6

Time Stamp End

Date (yy/mm/dd)

-

The Date this record was ended.

3

31407-8

Off Peak GVAh Net +/- 0…

9,999,999

Net Off peak giga VA hours

4

31409-10

Off Peak kVAh Net

+/- 0.000…

999,999

Net Off Peak kilo VA hours

5

31411-12

Off Peak kVA

Demand

+/- 0.000…

9,999,999

Off Peak Demand for kilo VA

6

31413-14

Mid Peak GVAh

Net

+/- 0…

9,999,999

Net Mid Peak giga VA hours

7

31415-16

Mid Peak kVAh Net +/- 0.000…

999,999

Net Mid Peak kilo VA hours

8

31417-18

Mid Peak kVA

Demand

+/- 0.000…

9,999,999

Mid Peak Demand for kilo VA

9

31419-20

On Peak GVAh Net

+/- 0.000…

9,999,999

Net On Peak giga VA hours

10

31421-22

On Peak kVAh Net

+/- 0…

999,999

Net On Peak kilo VA hours

11

31423-24

On Peak kVA

Demand

+/- 0.000…

9,999,999

On Peak Demand for kilo VA