beautypg.com

Daylight-savings time setup, Network time synchronization – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 38

background image

38

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Chapter 2 PowerMonitor 1000 Unit Features

Daylight-savings Time Setup

Daylight-savings time (DST) setup is done in the Advanced Setup menu. If DST

is enabled, the power monitor internal clock advances by one hour on the start

date and hour specified, and is set back by one hour on the return date and hour

specified. The defaults represent the common DST start and return date/times in

use in the United States in 2006. The DST function also adjusts the network-

time synch offset when used.

Network Time Synchronization

Network time synchronization is available only on units equipped with the

optional Ethernet network. Set-up parameters are found in the Ethernet

communication set-up menu. The power monitor updates its time from a simple

network time protocol (SNTP) server or an anycast group of SNTP servers,

depending on setup parameter values. Network-time synchronization set-up

parameters are found in the Ethernet communication set-up menu.

Parameter

Description

Range

Default

User Setting

Use DST Correction

0 = Disables DST

1 = Enables DST

0…1

0

DST Month/ Week/Day Start

Format: MMWWDD
Month:

01 = January…12 = December
Week:

01 = 1st week…05 = Last Week
Day of Week:

01 = Sunday…07 = Saturday

010101… 120507

030201

March, 2nd, Sunday

Hour of Day Start

0…23

2 (2 am)

Return from DST Month/ Week/Day

Format same as start date

010101… 120507

110101 November, First,

Sunday

Hour of Day End

0…23

2 (2 am)

Parameter

Description

Range

Default

User Setting

SNTP Mode Select

0 = Disable

1 = Unicast – Specify the IP address of a

unicast SNTP server.

2 = Anycast mode – Specify the broadcast

IP address of a SNTP anycast group.

0…2

0

SNTP Update Interval Defines how often the time is updated

from the SNTP server.

1…32766 minutes

300

Time Zone Select

There are 32 available time zones.

0…32

7 (Eastern Time)

Time Server IP

Address

Unicast server or anycast group IP

address in format aaa.bbb.ccc.ddd.

0.0.0.0…

255.255.255.255

0.0.0.0