Visualisation with »VisiWinNET®«
12.3
Using the visualisation to access data of the control/parameters
99
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.3
Using the visualisation to access data of the control/parameters
Variables of the PLC (Logic/Motion) can be accessed with the "LogicAndMotionV3" direct driver.
Here, the »VisiWinNET®« Runtime may be on a local controller or on an external controller.
Note!
We recommend the use of the "LogicAndMotionV3" direct driver for easy
commissioning.
Use the Direct driver "LogicAndMotionV3" (local visualisation)
There is no OPC server available for PROFIBUS and PROFINET.
Controller c300/p300:
• The OPC communication for »VisiWinNET« is exclusively available for Controller p300
without PLC.
• Otherwise, only the Lenze "Logic&Motion" direct driver can be used for the data
exchange between »VisiWinNET« and PLC.
Use the "LogicAndMotionV3" direct driver to
access the following parameters:
• PLC (Logic/Motion) data
• Lenze recommend to use the
"LogicAndMotionV3" direct driver.
• Alternatively, you can access the following
data via the OPC tunnel:
• DataManager OPC server
Controller parameters.
• CAN/EtherCAT OPC server
Field device parameters (CAN/
EtherCAT).
• SoftPLC OPC server
Variables of PLC (Logic/Motion):
Communication type / description
Access to ...
Direct driver "LogicAndMotionV3"
(Recommended connection type!)
Use the Direct driver "LogicAndMotionV3" (local
PLC (Logic/Motion) data
• DataManager OPC tunnel
• DataManager Remote OPC tunnel (remote access)
Parameters of the Controller