Voltage buffering by external UPS (optional, for Controller 3241 C)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C0212
C0213
C0214
Parameter | Name:
C0212 | UPS: Firmware version
Data type: VISIBLE_STRING
Index: 24363
d
= 5F2B
h
Version of the UPS firmware
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C0213 | UPS: Buffer time without action
Data type: UNSIGNED_16
Index: 24362
d
= 5F2A
h
The UPS buffers the system without any further action. If the voltage dip lasts longer than the time set here:
• The PLC is stopped.
• The PLC saves the retain variables, logbook entries and visualisation data (trends and alarms).
• The timer
is started.
Selection list
(Lenze setting printed in bold)
Info
0 0
250 250
500 500
750 750
1000 1000
1250 1250
1500 1500
1750 1750
2000 2000
2250 2250
2500 2500
2750 2750
3000 3000
3250 3250
3500 3500
3750 3750
4000 4000
4250 4250
4500 4500
4750 4750
5000 5000
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C0214 | UPS: Buffer time until shutdown
Data type: UNSIGNED_8
Index: 24361
d
= 5F29
h
After expiration of the time set here, the system is shut down. If the voltage is applied once again, the system is
restarted automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0
s
255 10 s
Read access Write access CINH PLC-STOP No transfer