Visualisation with »VisiWinNET®«
12.6
OPC tunnel for local visualisation (integrated control system)
115
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Communication types
Communication type
Description
DataManager OPC tunnel
Required information:
• Devicealias
• Parameterfile
Supported file formats:
• Device description files (*.dcf, *.eds)
Suitable device description files (*.eds) for the Controller 32xx can be found
in the Lenze Application Knowledge Base (AKB) under:
CAN OPC tunnel
Required information:
• CAN interface (CAN Interface)
• CAN node address (CAN Node Address)
• Devicealias
• Parameterfile
Supported file formats:
• Device description files (*.dcf, *.eds)
• Parameter description (*.pdb)
• »Global Drive Control« file(*.gdc)
EtherCAT OPC tunnel
Required information:
• EtherCAT interface (EtherCAT Interface)
• EtherCAT address (EtherCAT Node Address)
• Devicealias
• Parameterfile
Supported file format:
• Device description files (*.dcf, *.eds)
• Parameter file (*.pdb)
• »Global Drive Control« file (*.gdc)
Note: EtherCAT device description files (*.xml) are not supported!
SoftPLC OPC tunnel
Required information:
• The configuration name (Configuration Name) must be entered
manually. Default value of the Controller: PLC1.
Note: The configuration name must be identical to the specification in
the OPCServer.ini file!
• The OPCServer.ini file is on the memory card of the Controller (directory:
\USBStorage
).
Supported file format:
• Symbol file (*.sym)
Note: XML symbol configuration files exported from the »PLC
Designer« V3.x are not supported!
Manual integration of variables (experts only - background knowledge