9 data integrity in the event of a voltage failure, 1 ups functionality of the controllers, Data integrity in the event of a voltage failure – Lenze c300 User Manual
Page 68: Ups functionality of the controllers, 9data integrity in the event of a voltage failure
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
68
9
Data integrity in the event of a voltage failure
9.1
UPS functionality of the controllers
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9
Data integrity in the event of a voltage failure
9.1
UPS functionality of the controllers
9.1.1
Internal UPS (for Controllers without UPS connection)
In case of a voltage failure, retain/persistent variables, logbook data and visualisation data (e.g.
trends alarms) are saved.
The Controllers 3221 C/3231 C have an internal buffer capacitor for the short-time buffering of the
data.
The Controllers c300/p300/p500 are equipped with a high-capacity, internal UPS for the storage of
data in the event of a voltage failure. This makes external energy storage dispensable. Voltage
fluctuations cannot be compensated for.
The UPS behaviour of the internal UPS is preset. Parameter setting is not possible/required.
Controller
UPS functionality
Saves backup files to ...
3221 C
Internal capacitor for the short-time buffering of
data
MRAM (Magnetoresistive Random Access
Memory)
3231 C
3241 C
External battery pack (ACCU-PACK) or capacitor
pack (CAPS-PACK)
Memory card
c300
Internal capacitor
p300
p500