13 parameter reference – Lenze c300 User Manual
Page 181

13
Parameter reference
13.9
Communication cards: optional interface
181
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C1082
C1090
C1091
C1092
Parameter | Name:
C1082 | Baud rate
Data type: UNSIGNED_32
Index: 23493
d
= 5BC5
h
Baud rate of the CAN interface. The value is assigned from a selection list.
Selection list
(Lenze setting printed in bold)
7 5
6 10
5 20
3 50
8 100
2 125
1 250
0 500
4 1000
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1090 | Tx PDO counter
Data type: UNSIGNED_32
Index: 23485
d
= 5BBD
h
PDO counter for sent CAN messages
Display range
(min. value | unit | max. value)
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1091 | Rx PDO counter
Data type: UNSIGNED_32
Index: 23484
d
= 5BBC
h
PDO counter for received CAN messages
Display range
(min. value | unit | max. value)
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1092 | Bus load
Data type: UNSIGNED_32
Index: 23483
d
= 5BBB
h
Specification of the average bus load. The bus load is calculated as follows: Bus load = Value in percent x 1000
Display range
(min. value | unit | max. value)
Read access Write access CINH PLC-STOP No transfer