12 visualisation with »visiwinnet – Lenze c300 User Manual
Page 112
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
112
12
Visualisation with »VisiWinNET®«
12.6
OPC tunnel for local visualisation (integrated control system)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.6
OPC tunnel for local visualisation (integrated control system)
[12-2] Local visualisation on a controller
Note!
There is no OPC server available for PROFIBUS and PROFINET.
Controller c300/p300:
• The OPC communication for »VisiWinNET« is exclusively available for Controller p300
without PLC.
• Otherwise, only the Lenze "Logic&Motion" direct driver can be used for the data
exchange between »VisiWinNET« and PLC.
• The local »VisiWinNET®« Runtime on the
controller uses the local OPC tunnel to
access the respective OPC server
(DataManager, CAN/EtherCAT, SoftPLC).
• For a local visualisation, the OPCServer.ini
configuration file must be adapted. The
configuration file is on the memory card of
the controller, directory: \USBStorage.