7 error messages (backplane bus), Error messages (backplane bus), 5commissioning the controller – Lenze c300 User Manual
Page 43
5
Commissioning the controller
5.7
Error messages (backplane bus)
43
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.7
Error messages (backplane bus)
Error messages are represented on the Diagnostics tab of the I/O module coupler.
[5-5]
Example: Topology error, the EPM-S501 module cannot be reached at the backplane bus.
Error messages
The following error messages can be displayed:
Error number
Error text/remedy
11
Too many I/O modules for the task cycle time selected.
• Increase cycle time.
12
FIFO response full.
• Contact Lenze
32
Timeout reset
• Contact Lenze
33
Timeout reset error
• Contact Lenze
96
Too many I/O modules for the task cycle time selected.
• Increase cycle time.
97
Too many I/O modules for the task cycle time selected.
• Increase cycle time.
98
Too many I/O modules for the task cycle time selected.
• Increase cycle time.
99
Too many I/O modules for the task cycle time selected.
• Increase cycle time.
100
Too many I/O modules for the task cycle time selected.
• Increase cycle time.
101
Timeout for master queue operation
• Contact Lenze
102
Bus initialisation error with one I/O module
• Contact Lenze
103
Master queue operation error
• Not all I/O modules can be reached.
104
Read semaphore timeout for group 1
105
Read semaphore timeout for group 2
106
Read semaphore timeout for group 3
107
Write semaphore timeout for group 1
108
Write semaphore timeout for group 2
109
Write semaphore timeout for group 3
110
Internal error of the backplane bus hardware
• Contact Lenze
116
Read semaphore timeout for group 1