Voltage, 13 parameter reference – Lenze c300 User Manual
Page 158
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
158
13
Parameter reference
13.3
Voltage buffering by external UPS (optional, for Controller 3241 C)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.3
Voltage buffering by external UPS (optional, for Controller 3241 C)
This chapter lists all UPS parameters in numerically ascending order.
UPS functionality of the controllers
C0203
C0204
C0205
Parameter | Name:
C0203 | UPS: UPS monitoring
Data type: UNSIGNED_8
Index: 24372
d
= 5F34
h
Enable monitoring via an external UPS (optional)
Selection list
(Lenze setting printed in bold)
Info
0 Off
1 On
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C0204 | UPS: Status
Data type: UNSIGNED_8
Index: 24371
d
= 5F33
h
Status of the external UPS
Selection list
(read only)
Info
0 ACU Controller is missing
85 Battery / capacitor is loaded
86 Battery / capacitor is being loaded
87 -
88 -
89 UPS is buffering the system
90 Battery / capacitor short circuit
91 Battery / capacitor is missing
92 Battery / capacitor is defective
93 ACU Controller is defective
94 -
95 Undefined status of battery /
capacitor
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C0205 | UPS: Supply voltage
Data type: FLOAT_32
Index: 24370
d
= 5F32
h
Supply voltage of the external UPS in [V]
Display range
(min. value | unit | max. value)
0
V
34
Read access Write access CINH PLC-STOP No transfer