4 Electrical connection

4.3.3

Terminating resistors

The internal terminating resistors for the Com1 and Com2 interfaces are only relevant for
RS422/485.
The terminating resistors are deactivated by default. To activate them, DIP switches 1 to 4 for
the relevant interface must be pushed upward using a suitable tool such as a ballpoint pen (ON
position).
The following figure shows the position of the DIP switches when the terminating resistors are
activated.

Internal terminating resistors

4.3.4

Voltage supply

2

1

3

4

ON

NOTE!
To ensure fault-free operation, terminating resistors are required at the start and end of an
RS422/485 transmission path.

332

?

120

?

332

?

GND

+5 V

4

9

332

?

120

?

332

?

GND

+5 V

3

4

3

8

1

2

Connection

Terminals

Symbol and terminal designation

24 V DC

+24 V and GND

+24 V

GND