13 Configuration

Type; Additional storage

"Yearly" or "Total" selection: The status of the counter/integrator is cached at the end of a
month, but not reset to 0. This means that the current status is always available at such a point
in time for evaluation using the PCA3000 evaluation software.

Evaluation

"Counter" function: The counter status is increased by the "Evaluation" value with
each digital signal pulse. A negative value can be used to form a backwards coun-
ter.

"Integrator" function: The current measured value of the analog or integer signals
is multiplied by the "Evaluation" factor and added to the result.

-3.37E+38 to 1 to +9.0E+36

Value or factor

Time base

"Integrator" function: The current measured value is integrated corresponding to
the selected time base, taking into consideration the evaluation:

Second

The measured value is divided by 1 and
added up every second.

Minute

The measured value is divided by 60
and added up every second.

Hour

The measured value is divided by 3600
and added up every second.

Day

The measured value is divided by 86400
and added up every second.

"Operating time" function: The time base specifies the unit in which the operation
time is displayed:

Second

Display in seconds

Minute

Display in minutes

Hour

Display in hours

Day

Display in days

Threshold

"Integrator" function: An integration only takes place if the current measured value
is greater than the threshold value. Time base and evaluation are not included in
the threshold comparison.

0.00000000 to 999999999

Threshold

Reset signal

The reset signal is used to set the counter and integrator statuses to 0 (indepen-
dent of other parameters). The current status is not saved in the process.

This reset signal is available in addition to the reset signal described in Chapter
13.17.1 "General settings", page 182.

Inactive

No signal selected.

Digital selector

The signal (high active) can be selected
from the list of digital signals.

Parameter

Selection/settings

Description