13 Configuration

154

13.11.3 Counters/Integrators

Setup dialog

Parameter

Counter/Integrator

Here, a maximum of 4 of the 27 total available counters/integrators can be assigned to each
group. The allocation of the counters to a group means that counter alarms and integrator
alarms can be allocated to the batches and entered in the corresponding alarm and event lists.
All 27 counters can be read out in each group in the PCA3000 evaluation software. The 4 allo-
cated here are visible by default and the remainder can be shown if desired.

Parameter

Selection/settings

Description

Counter/Integra-
tor

4 counters or integrators can be assigned to each of the 9 groups.

Inactive

No signal allocated.

Counter/Int. X

Signal that is to be assigned to the
counter/integrator.

?