13 Configuration

140

Parameter

Alarm type and switching differential

Parameter

Selection/settings

Description

Alarm type 1, 2

Inactive

Monitoring is not active.

Min. Alarm

Alarm is issued if the limit value is not
met.

Max. Alarm

Alarm is issued if the limit value is
exceeded.

Limit value 1, 2

-99999 to 0 to +99999

Limit value at which an alarm is issued.

Alarm text 1, 2

Use default text or enter other text.

Text that is displayed or entered in the
status and title line and in the alarm list
and event list in the case of an alarm.

Switching differ-
ential

0 to 99999

Used to reject constant switching opera-
tions in the event of minor fluctuations of
the input signal around the limit value

Alarm rejection

Inactive

Digital selector

Signal for activating the alarm rejection

Alarm delay

0 s to 65535 s

Delay time for alarm triggering

?

?

(1)

(2)

(3)

(3)

1

0

(1) Min. alarm/limit value

1 Alarm on

(2) Max. alarm/limit value

0 Alarm off

(3) Switching differential