13 Configuration

164

External

Synchronizat. time

The Synchronizat. time parameter will be explained in more detail below, using the example of
a periodical report.

The stop and restart is performed at the next point in time occurring in the time grid – dependent
on Synchronizat. time and Period.

Example:
Period = 2 hours
Synchronizat. time = 11:30:00
Power on = 09:11:00

1st period from 09:11 to 09:30 = 19 minutes
2nd period from 09:30 to 11:30 = 2 hours
3rd period from 11:30 to 13:30 = 2 hours
etc.

NOTE!
Within 5 seconds, only one external report is started in a group, i.e. a new external start prior
to 5 seconds having elapsed will be ignored. If the start signal is still on after 5 seconds, the
external report is started immediately. If the start signal is no longer on, the report will be not
be restarted.

NOTE!
The principle is the same for all reports relating to the synchronization time (daily, weekly,
and periodical report). For a daily report, the first report will usually not run for 24 hours and
the first weekly report will usually not run for 7 days.