Compare function – Watlow EZ-ZONE RME User Manual

Page 95

background image

Watlow EZ-ZONE

®

RME Module

92

Chapter 6 Features

IF Type = Off THEN Output Value = OFF Alarm
State = None and Alarm Indication = None

Alarm

Off

IF Type = Process THEN Alarm Variable = Process
Value

Alarm Latching

Alarm Blocking

Alarm Silencing

Alarm Hysteresi

s

Alarm Clear Reques

t

Alarm Silence Reques

t

Alarm

Typ

e

Alarm Logi

c

Alarm Side

s

Alarm Displa

y

Alarm Delay

Time

Alarm Low Set

Point

Alarm High Set

Point

Output Value

Alarm Clearable

Alarm Working Process Value

Alarm Working Set Point

Alarm Latched

Alarm Silenced

Alarm State

Error

Alarm Source
Alarm Source Instance
Alarm Source Zone
Alarm Source Error

Alarm

Process

Alarm Latching

Alarm Blocking

Alarm Silencing

Alarm Hysteresi

s

Alarm Clear Reques

t

Alarm Silence Reques

t

Alarm

Type

Alarm Logi

c

Alarm Side

s

Alarm Displa

y

Alarm Delay

Time

Alarm Low Set

Point

Alarm High Set

Point

Output Value

Alarm Clearable

Alarm Working Process Value

Alarm Working Set Point

Alarm Latched

Alarm Silenced

Alarm State

Error

Alarm Source
Alarm Source Instance
Alarm Source Zone
Alarm Source Error

Compare Function

Use this function to compare Source A to Source

B and then drive the output based on the compari-

son. For the function to work properly, Source A and

Source B must be without errors.
An error, when read, can indicate any of the follow-

ing: None, Open, Shorted, Measurement Error, Bad

Cal Data, Ambient Error, RTD Error, Fail, Math Er-

ror, Not Sourced, Stale
Tolerance is expressed in the same units as Source

A.

[SFn;A]

Source Function A : None, Analog Input, Current, Cool Power, Heat

Power, Power, Linearization, Math, Process Value, Set Point Closed,

Set Point Open, Variable

[SFn;b]

Source Function B : None, Analog Input, Current, Cool Power,

Heat Power, Power, Linearization, Math, Process Value,

Set Point Closed, Set Point Open, Variable

[`S2;A

] Source Zone A : 0 to 16

[`S2;b]

Source Zone B : 0 to 16

[`Si;A]

Source Instance A : 1 to 250

Compare

Overview

Instances - 8 per RME

Tolerance

Error Handling

Function

[``Fn]

Function : Off, Greater Than, Less Than, Equal To, Not Equal To,

Greater or Equal , Less or Equal

[`CPE]

Compare Menu

[`SEt]

Setup Page

[`Si;b]

Source Instance B : 1 to 250

[`Er;h]

Error Handling : False Bad, False Good, True Bad, True Good

[`CPE]

Compare Menu

[oPEr]

Operation Page

[`Su;A]

Source Value A : -1,999.000 to 9,999.000 units or F

[`Su;b]

Source Value B : -1,999.000 to 9,999.000 units or F

[``o;u]

Output Value : Off, On

Output Value

Error

Source Value A

Source Value B

Source Function A
Source Instance A
Source Zone A
Source Error A

Source Function B
Source Instance B
Source Zone B
Source Error B

[`toL]

Tolerance : 0.0 to 9,999.000 units or F

No Compare, Output Value = OFF

Tolerance

Error Handling

Function

Output Value

Error

Source Value A

Source Value B

Source Function A
Source Instance A
Source Zone A
Source Error A

Source Function B
Source Instance B
Source Zone B
Source Error B

Compare

Off