Watlow EZ-ZONE

®

RME Module

75

Chapter 4 Setup Page

RME Module

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[`o;S2]
[ o.S2]

Special Output (1 to 8)

Output 2 Size

If Function is set to Se-

quencer:

• Set the size of outputs 2

through 4 to represent

a percentage of the

total output capacity.

Outputs 2 through 4

will control using the

ON-OFF algorithm.

0 to 9,999

0

6676

[offset 80]

0x87 (135)

1 to 4

0x1D (29)

- - - -

35029

float
RWES

[`o;S3]
[ o.S3]

Special Output (1 to 8)

Output 3 Size

If Function is set to Se-

quencer:

• Set the size of outputs 2

through 4 to represent

a percentage of the

total output capacity.

Outputs 2 through 4

will control using the

ON-OFF algorithm.

0 to 9,999

0

6678

[offset 80]

0x87 (135)

1 to 4

0x1E (30)

- - - -

35030

float
RWES

[`o;S4]
[ o.S4]

Special Output (1 to 8)

Output 4 Size

If Function is set to Se-

quencer:

• Set the size of outputs 2

through 4 to represent

a percentage of the

total output capacity.

Outputs 2 through 4

will control using the

ON-OFF algorithm.

0 to 9,999

0

6680

[offset 80]

0x87 (135)

1 to 4

0x1F (31)

- - - -

35031

float
RWES

[`t;dL]
[ t.dL]

Special Output (1 to 8)

Time Delay

If Function is set to Se-

quencer:

• Set in seconds to repre-

sent the minimum span

of time that must elapse

between the turn on of

one (on-off) output to

the next.

0 to 9,999 seconds

0

6670

[offset 80]

0x87 (135)

1 to 4

0x1A (26)

- - - -

35026

uint
RWES

[`ot;o]
[ ot.o]

Special Output (1 to 8)

Output Order

If Function is set to Se-

quencer:

• Set to Linear to turn

the on-off outputs on in

the same order every

time. Select Progres-

sive to rotate the order

to balance usage and

wear on contactors and

heaters.

[`Lin]

Linear (1509)

[`Pro]

Progressive (1510)

Linear

6672

[offset 80]

0x87 (135)

1 to 4

0x1B (27)

- - - -

35027

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display . Full values can be read

with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set