beautypg.com

Watlow EZ-ZONE RME User Manual

Page 48

background image

Watlow EZ-ZONE

®

RME Module

45

Chapter 4 Setup Page

RME Module

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[``s2]
[ SZ]

Output Digital (1 to 4, 7 to

10, 13 to 16, 19 to 22)

Source Zone

Set the instance of the

function selected above.

0 to 16

0

382
[offset 30]

0x6A (106)

1 to (24)

0x0C (12)

- - - -

6012

uint
RWES

[`o;Ct]
[ o.Ct]

Output Digital (1 to 4, 7 to

10, 13 to 16, 19 to 22)

Control

Set the output control type.

This parameter is only

used with PID control, but

can be set anytime.

[`Ftb]

Fixed Time Base

(34)

[`utb]

Variable Time Base

(103)

Fixed

Time

Base

362
[offset 30]

0x6A (106)

1 to (24)

2

- - - -

6002

uint
RWES

[`o;tb]
[ o.tb]

Output Digital (1 to 4, 7 to

10, 13 to 16, 19 to 22)

Time Base

Set the time base for fixed-

time-base control.

0.1 to 60.0 seconds (solid-

state relay or switched dc)

5.0 to 60.0 seconds (me-

chanical relay or no-arc

power control)

364
[offset 30]

0x6A (106)

1 to (24)

3

- - - -

6003

float
RWES

[`o;Lo]
[ o.Lo]

Output Digital (1 to 4, 7 to

10, 13 to 16, 19 to 22)

Low Power Scale

The power output will nev-

er be less than the value

specified and will represent

the value at which output

scaling begins.

0.0 to 100.0%

0.0%

376
[offset 30]

0x6A (106)

1 to (24)

9

- - - -

6009

float
RWES

[`o;hi]
[ o.hi]

Output Digital (1 to 4, 7 to

10, 13 to 16, 19 to 22)

High Power Scale

The power output will

never be greater than the

value specified and will

represent the value at

which output scaling stops.

0.0 to 100.0%

100.0%

378
[offset 30]

0x6A (106)

1 to (24)

0x0A (10)

- - - -

6010

float
RWES

[`o;ty]
[ o.ty]

Output Process (1 to 3, 7 to

9, 13 to 15, 19 to 21)

Type **

Select whether the process

output will operate in volts

or milliamps.

[uoLt]

Volts (104)

[`MA]

Milliamps (112)

Volts

6990
[offset 60]

0x76 (118)

1-3, 7-9,

13-15, 19-

21

1

- - - -

18001

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display . Full values can be read

with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S: