Watlow EZ-ZONE RME User Manual
Page 48

Watlow EZ-ZONE
®
RME Module
•
45
•
Chapter 4 Setup Page
RME Module
•
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[``s2]
[ SZ]
Output Digital (1 to 4, 7 to
10, 13 to 16, 19 to 22)
Source Zone
Set the instance of the
function selected above.
0 to 16
0
382
[offset 30]
0x6A (106)
1 to (24)
0x0C (12)
- - - -
6012
uint
RWES
[`o;Ct]
[ o.Ct]
Output Digital (1 to 4, 7 to
10, 13 to 16, 19 to 22)
Control
Set the output control type.
This parameter is only
used with PID control, but
can be set anytime.
[`Ftb]
Fixed Time Base
(34)
[`utb]
Variable Time Base
(103)
Fixed
Time
Base
362
[offset 30]
0x6A (106)
1 to (24)
2
- - - -
6002
uint
RWES
[`o;tb]
[ o.tb]
Output Digital (1 to 4, 7 to
10, 13 to 16, 19 to 22)
Time Base
Set the time base for fixed-
time-base control.
0.1 to 60.0 seconds (solid-
state relay or switched dc)
5.0 to 60.0 seconds (me-
chanical relay or no-arc
power control)
364
[offset 30]
0x6A (106)
1 to (24)
3
- - - -
6003
float
RWES
[`o;Lo]
[ o.Lo]
Output Digital (1 to 4, 7 to
10, 13 to 16, 19 to 22)
Low Power Scale
The power output will nev-
er be less than the value
specified and will represent
the value at which output
scaling begins.
0.0 to 100.0%
0.0%
376
[offset 30]
0x6A (106)
1 to (24)
9
- - - -
6009
float
RWES
[`o;hi]
[ o.hi]
Output Digital (1 to 4, 7 to
10, 13 to 16, 19 to 22)
High Power Scale
The power output will
never be greater than the
value specified and will
represent the value at
which output scaling stops.
0.0 to 100.0%
100.0%
378
[offset 30]
0x6A (106)
1 to (24)
0x0A (10)
- - - -
6010
float
RWES
[`o;ty]
[ o.ty]
Output Process (1 to 3, 7 to
9, 13 to 15, 19 to 21)
Type **
Select whether the process
output will operate in volts
or milliamps.
[uoLt]
Volts (104)
[`MA]
Milliamps (112)
Volts
6990
[offset 60]
0x76 (118)
1-3, 7-9,
13-15, 19-
21
1
- - - -
18001
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be read
with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set