Chapter 4 Setup Page
RME Module
•
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[sfn;A]
[SFn.A]
Action (1 to 8)
Source Function A
Set the event or function
that will trigger the action.
[nonE]
None (61)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out
A (233)
[Ent;b]
Profile Event Out
B (234)
[Ent;C]
Profile Event Out
C (235)
[Ent;d]
Profile Event Out
D (236)
[Ent;E]
Profile Event Out
E (247)
[Ent;F]
Profile Event Out
F (248)
[Ent;g]
Profile Event Out
G (249)
[Ent;h]
Profile Event Out
H (250)
[`FUn]
Function Key
(1001)
[lim]
Limit (126)
[`lgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
1290
[offset 20]
0x6E (110)
1 to 8
6
- - - -
10006
uint
RWES
[`si;a]
[ Si.A]
Action (1 to 8)
Source Instance A
Set the instance of the
function selected above.
1 to 250
1
1282
[offset 20]
0x6E (110)
1 to 8
2
- - - -
10002
uint
RWES
[`52;A]
[ SZ.A]
Action (1 to 8)
Source Zone A
Set the zone of the function
selected above.
0 to 16
0
1292
[offset 20]
0x6E (110)
1 to 8
7
- - - -
10007
uint
RWES
[`LEu]
[ LEv]
Action (1 to 8)
Active Level
Set the action that will be
considered a true state.
[LoW]
Low (53)
[high]
High (37)
High
1280
[offset 20]
0x6E (110)
1 to 8
1
137
10001
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be read
with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S: