Chapter 4 Setup Page

RME Module

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[sfn;A]
[SFn.A]

Action (1 to 8)

Source Function A

Set the event or function

that will trigger the action.

[nonE]

None (61)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out

A (233)

[Ent;b]

Profile Event Out

B (234)

[Ent;C]

Profile Event Out

C (235)

[Ent;d]

Profile Event Out

D (236)

[Ent;E]

Profile Event Out

E (247)

[Ent;F]

Profile Event Out

F (248)

[Ent;g]

Profile Event Out

G (249)

[Ent;h]

Profile Event Out

H (250)

[`FUn]

Function Key

(1001)

[lim]

Limit (126)

[`lgC]

Logic (239)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

1290
[offset 20]

0x6E (110)

1 to 8

6

- - - -

10006

uint
RWES

[`si;a]
[ Si.A]

Action (1 to 8)

Source Instance A

Set the instance of the

function selected above.

1 to 250

1

1282
[offset 20]

0x6E (110)

1 to 8

2

- - - -

10002

uint
RWES

[`52;A]
[ SZ.A]

Action (1 to 8)

Source Zone A

Set the zone of the function

selected above.

0 to 16

0

1292
[offset 20]

0x6E (110)

1 to 8

7

- - - -

10007

uint
RWES

[`LEu]
[ LEv]

Action (1 to 8)

Active Level

Set the action that will be

considered a true state.

[LoW]

Low (53)

[high]

High (37)

High

1280
[offset 20]

0x6E (110)

1 to 8

1

137

10001

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display . Full values can be read

with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S: