Quencharc wiring example, Dual 10a ssr outputs 1-4, L_ k – Watlow EZ-ZONE RME User Manual

Page 26

background image

Watlow EZ-ZONE

®

RME Module

23

Chapter 2 Install and Wire

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination
and torque rating:
• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination
or two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be la-
beled differently, depending on
the model number.

Note:

To prevent damage to the con-
troller, do not connect wires to
unused terminals.

Note:

Maintain electrical isolation
between digital input-outputs,
switched dc/open collector out-
puts and process outputs to

prevent ground loops.

Note:

If the last two digits of the part
number are "12", this equip-
ment is suitable for use in
CLASS I, DIVISION 2, Groups
A, B, C and D or Non-Hazard-
ous locations only. Temperature

Code T4

Warning:

ç

Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.

Warning:

ç

Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.

Quencharc Wiring Example

In this example the
Quencharc circuit (Watlow
part# 0804-0147-0000) is
used to protect the RME
internal circuitry from the
counter electromagnetic force
from the inductive user load
when de-engergized. It is
recommended that this or an
equivalent Quencharc be used
when connecting inductive
loads to the RME outputs.

Quencharc

User Load

L_

K_

N

Dual 10A SSR Outputs 1-4

RME Part # Digit 5 or 7 is K

normally open

common

L1
L1

K1
K1

L2
L2

K2
K2

Slot A

normally open

common

normally open

common

normally open

common

• Maximum resistive load 10

A per output @ 240V (ac)

• Maximum 20 A per slot @

50

0

C

• Maximum 12 A per slot @

65

0

C

Normally Open

Normally Open

Common

Common

L_

L_

L_

L_

K_

K_

K_

K_

normally open

common

L13
L13

K13
K13

L14
L14

K14
K14

Slot D

normally open

common

normally open

common

normally open

common

Total Output Amps Per Slot

15

10

5

0

20

55

50

45

40

35

30

25

60

65

Output Amps

Ambient Temperatue (

o

C)

20

12 A

70

25