Linearization menu – Watlow EZ-ZONE RME User Manual
Page 53
Watlow EZ-ZONE
®
RME Module
•
50
•
Chapter 4 Setup Page
RME Module
•
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[`C;SC]
[ C.SC]
Current (1 to 4)
Scaling
Use Input Current Scaling
to adjust scaling to match
the transformer's high
range, in amperes.
0 to 9,999.000
50.0
1122
[offset 50]
0x73 (115)
1 to 4
0x16 (22)
148
15022
float
RWES
[C;;oFs]
[C.oFS]
Current (1 to 4)
Heater Offset
Heater Current Offset is
used to calibrate the cur-
rent reading with an offset
value.
-9,999.000 to 9,999.000
0.0
1100
[offset 50]
0x73 (115)
1 to 4
0xB (11)
149
15011
float
RWES
[`C;;Si]
[ C.Si]
Current (1 to 4)
Output Source Instance
With Current Output
Source Instance, set the
output on which the cur-
rent will be monitored.
1 to 250
1
1116
[offset 50]
0x73 (115)
1 to 4
0x13 (19)
150
15019
uint
RWES
[``S2]
[ SZ]
Current (1 to 4)
Source Zone
Set the zone of the function
selected above.
0 to 16
0
- - - -
- - - -
- - - -
15036
uint
RWES
[`Lnr]
[`Set]
Linearization Menu
[``Fn]
[ Fn]
Linearization (1 to 8)
Function
Set how this function will
linearize Source A.
[`oFF]
Off (62)
[intr]
Interpolated (1482)
[Stpd]
Stepped (1483)
Off
5548
[offset 70]
0x86 (134)
1 to 8
5
155
34005
uint
RWES
[`s2;A]
[ SZ.A]
Linearization (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 or 16
0
5544
[offset 70]
0x86 (134)
1 to 8
3
- - - -
34003
uint
RWES
[Unit]
[Unit]
Linearization (1 to 8)
Units
Set the units of Source A.
[`Src]
Source (1539)
[nonE]
None (61)
[`A;tP]
Absolute Tempera-
ture (1540)
[`r;tp]
Relative Tempera-
ture (1541)
[PWr]
Power (73)
[`pro]
Process (75)
[``rh]
Relative Humidty
(1538)
Source
5596
[offset 70]
0x86 (134)
1 to 8
0x1D (29)
- - - -
34029
uint
RWES
[`iP;1]
[ ip.1]
Linearization (1 to 8)
Input Point 1
Set the value that will be
mapped to output 1.
-1,999.000 to 9,999.000
0.0
5554
[offset 70]
0x86 (134)
1 to 8
8
157
34008
float
RWES
[`oP;1]
[ op.1]
Linearization (1 to 8)
Output Point 1
Set the value that will be
mapped to input 1.
-1,999.000 to 9,999.000
0.0
5574
[offset 70]
0x86 (134)
1 to 8
0x12 (18)
158
34018
float
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be read
with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set