Linearization menu – Watlow EZ-ZONE RME User Manual

Page 53

background image

Watlow EZ-ZONE

®

RME Module

50

Chapter 4 Setup Page

RME Module

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[`C;SC]
[ C.SC]

Current (1 to 4)

Scaling

Use Input Current Scaling

to adjust scaling to match

the transformer's high

range, in amperes.

0 to 9,999.000

50.0

1122

[offset 50]

0x73 (115)

1 to 4

0x16 (22)

148

15022

float
RWES

[C;;oFs]
[C.oFS]

Current (1 to 4)

Heater Offset

Heater Current Offset is

used to calibrate the cur-

rent reading with an offset

value.

-9,999.000 to 9,999.000

0.0

1100

[offset 50]

0x73 (115)

1 to 4

0xB (11)

149

15011

float
RWES

[`C;;Si]
[ C.Si]

Current (1 to 4)

Output Source Instance

With Current Output

Source Instance, set the

output on which the cur-

rent will be monitored.

1 to 250

1

1116

[offset 50]

0x73 (115)

1 to 4

0x13 (19)

150

15019

uint
RWES

[``S2]
[ SZ]

Current (1 to 4)

Source Zone

Set the zone of the function

selected above.

0 to 16

0

- - - -

- - - -

- - - -

15036

uint
RWES

[`Lnr]
[`Set]
Linearization Menu

[``Fn]
[ Fn]

Linearization (1 to 8)

Function

Set how this function will

linearize Source A.

[`oFF]

Off (62)

[intr]

Interpolated (1482)

[Stpd]

Stepped (1483)

Off

5548

[offset 70]

0x86 (134)

1 to 8

5

155

34005

uint
RWES

[`s2;A]
[ SZ.A]

Linearization (1 to 16)

Source Zone A

Set the zone of the function

selected above.

0 or 16

0

5544

[offset 70]

0x86 (134)

1 to 8

3

- - - -

34003

uint
RWES

[Unit]
[Unit]

Linearization (1 to 8)

Units

Set the units of Source A.

[`Src]

Source (1539)

[nonE]

None (61)

[`A;tP]

Absolute Tempera-

ture (1540)

[`r;tp]

Relative Tempera-

ture (1541)

[PWr]

Power (73)

[`pro]

Process (75)

[``rh]

Relative Humidty

(1538)

Source

5596

[offset 70]

0x86 (134)

1 to 8

0x1D (29)

- - - -

34029

uint
RWES

[`iP;1]
[ ip.1]

Linearization (1 to 8)

Input Point 1

Set the value that will be

mapped to output 1.

-1,999.000 to 9,999.000

0.0

5554

[offset 70]

0x86 (134)

1 to 8

8

157

34008

float
RWES

[`oP;1]
[ op.1]

Linearization (1 to 8)

Output Point 1

Set the value that will be

mapped to input 1.

-1,999.000 to 9,999.000

0.0

5574

[offset 70]

0x86 (134)

1 to 8

0x12 (18)

158

34018

float
RWES

Note:

Some values will be rounded off to fit in the four-character display . Full values can be read

with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set