beautypg.com

Watlow EZ-ZONE RME User Manual

Page 73

background image

Watlow EZ-ZONE

®

RME Module

70

Chapter 4 Setup Page

RME Module

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[sfn;D]
[SFn.d]

Math (1 to 8)

Source Function D

Set the type of function

that will be used for this

source.

[nonE]

None (61)

[``Ai]

Analog Input (142)

[CUrr]

Current (22)

[`C;Pr]

Cool Power, Control

Loop (161)

[`h;Pr]

Heat Power, Control

Loop (160)

[PWr]

Power, Control Loop

(73)

[`Lnr]

Linearization (238)

[MAt]

Math (240)

[``Pu]

Process Value (241)

[`SP;C]

Set Point Closed,

Control Loop (242)

[`SP;o]

Set Point Open,

Control Loop (243)

[`uAr]

Variable (245)

2186

[offset 70]

0x7D (125)

1 to 8

4

- - - -

25004

uint
RWES

[`si;D]
[ iS.d]

Math (1 to 8)

Source Instance D

Set the instance of the

function selected above.

1 to 250

1

2196

[offset 70]

0x7D (125)

1 to 8

9

- - - -

25009

uint
RWES

[`s2;D]
[ SZ.d]

Math (1 to 8)

Source Zone D

Set the zone of the function

selected above.

0 to 16

0

2206

[offset 70]

0x7D (125)

1 to (16)

0x0E (14)

- - - -

25014

uint
RWES

[sfn;E]
[ Sr.E]

Math (1 to 8)

Source Function E

Set the type of function

that will be used for this

source.

[none]

None (61)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out

A (233)

[Ent;b]

Profile Event Out

B (234)

[Ent;C]

Profile Event Out

C (235)

[Ent;d]

Profile Event Out

D (236)

[Ent;E]

Profile Event Out

E (247)

[Ent;F]

Profile Event Out

F (248)

[Ent;g]

Profile Event Out

G (249)

[Ent;h]

Profile Event Out

H (250)

[`FUn]

Function Key

(1001)

[`lgC]

Logic (239)

[tMr]

Timer (244)

[`uAr]

Variable (245))

None

2188

[offset 70]

0x7D (125)

1 to 8

5

- - - -

25005

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display . Full values can be read

with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set