beautypg.com

Current menu – Watlow EZ-ZONE RME User Manual

Page 35

background image

Watlow EZ-ZONE

®

RME Module

32

Chapter 3 Operations Page

RME Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[A;sir]
[A.Sir]

Alarm (1 to 4)

Alarm Silence Request

Write to this register to

silence an alarm

0

None

1466
[offset 60]

0x6D

(109)

1 to 8

0xE (14)

15

9014

uint

W

[`a;st]
[ A.St]

Alarm (1 to 8)

Alarm State

View state of alarm

Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)

None

1456
[offset 60]

0x6D

(109)

1 to 8

9

- - - -

9009

uint

R

No Dis-

play

Alarm (1 to 4)

Alarm Clearable

Read to determine if

alarm can be cleared.

[``no]

No (59)

[`YES]

Yes (106)

None

1462
[offset 60]

0x6D

(109)

1 to 8

0xC (12)

- - - -

9012

uint

R

No Dis-

play

Alarm (1 to 8)

Silenced

Read to see if alarm is ac-

tive but has been silenced

by Alarm Silence Request.

Yes (106)

No (59)

- - - -

1460
[offset 60]

0x6D

(109)

1 to 4

0x0B (11)

- - - -

9011

uint

R

No Dis-

play

Alarm (1 to 8)

Latched

Read to see if alarm is

currently latched.

Yes (106)

No (59)

- - - -

1458
[offset 60]

0x6D

(109)

1 to 4

0x0A (10)

- - - -

9010

uint

R

[CUrr]]
[oPEr]]
Current Menu

Note: To use the current sensing feature, Time Base (Setup

Page, Output Menu) must be set to 0 .7 seconds or more .

[`C;hi]
[ C.hi]

Current (1 to 4)

High Set Point

Set the current value that

will trigger a high heater

error state.

-1,999.000 to 9,999.000

50.0

1094
[offset 50]

0x73

(115)

1 to 4

8

- - - -

15008

float
RWES

[`C;Lo]
[ C.Lo]

Current (1 to 4)

Low Set Point

Set the current value that

will trigger a low heater

error state.

-1,999.000 to 9,999.000

0.0

1096
[offset 50]

0x73

(115)

1 to 4

9

- - - -

15009

float
RWES

[`CU;r]
[ CU.r]

Sensed Current (1 to 4)

Read

View the most recent cur-

rent value monitored by

the current transformer.

-1,999.000 to 9,999.000

- - - -

1080
[offset 50]

0x73

(115)

1 to 4

1

- - - -

15001

float
R

[`C;Er]
[ C.Er]

Current (1 to 4)

Error

View the cause of the

most recent load fault.

[nonE]

None (61)

[Shrt]

Shorted (127)

[open]

Open (65)

- - - -

1082
[offset 50]

0x73

(115)

1 to 4

2

- - - -

15002

uint
R

[`h;Er]
[ h.Er]

Current (1 to 4)

Heater Error

View the cause of the

most recent load fault

monitored by the current

transformer.

[nonE]

None (61)

[high]

High (37)

[Low]

Low (53)

- - - -

1084
[offset 50]

0x73

(115)

1 to 4

3

- - - -

15003

uint
R

Note:

Some values will be rounded off to fit in the four-character display . Full values can be

read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E: EE-

PROM

S: User

Set