Chapter 3 Operations Page
RME Module
•
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[A;sir]
[A.Sir]
Alarm (1 to 4)
Alarm Silence Request
Write to this register to
silence an alarm
0
None
1466
[offset 60]
0x6D
(109)
1 to 8
0xE (14)
15
9014
uint
W
[`a;st]
[ A.St]
Alarm (1 to 8)
Alarm State
View state of alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
None
1456
[offset 60]
0x6D
(109)
1 to 8
9
- - - -
9009
uint
R
No Dis-
play
Alarm (1 to 4)
Alarm Clearable
Read to determine if
alarm can be cleared.
[``no]
No (59)
[`YES]
Yes (106)
None
1462
[offset 60]
0x6D
(109)
1 to 8
0xC (12)
- - - -
9012
uint
R
No Dis-
play
Alarm (1 to 8)
Silenced
Read to see if alarm is ac-
tive but has been silenced
by Alarm Silence Request.
Yes (106)
No (59)
- - - -
1460
[offset 60]
0x6D
(109)
1 to 4
0x0B (11)
- - - -
9011
uint
R
No Dis-
play
Alarm (1 to 8)
Latched
Read to see if alarm is
currently latched.
Yes (106)
No (59)
- - - -
1458
[offset 60]
0x6D
(109)
1 to 4
0x0A (10)
- - - -
9010
uint
R
[CUrr]]
[oPEr]]
Current Menu
Note: To use the current sensing feature, Time Base (Setup
Page, Output Menu) must be set to 0 .7 seconds or more .
[`C;hi]
[ C.hi]
Current (1 to 4)
High Set Point
Set the current value that
will trigger a high heater
error state.
-1,999.000 to 9,999.000
50.0
1094
[offset 50]
0x73
(115)
1 to 4
8
- - - -
15008
float
RWES
[`C;Lo]
[ C.Lo]
Current (1 to 4)
Low Set Point
Set the current value that
will trigger a low heater
error state.
-1,999.000 to 9,999.000
0.0
1096
[offset 50]
0x73
(115)
1 to 4
9
- - - -
15009
float
RWES
[`CU;r]
[ CU.r]
Sensed Current (1 to 4)
Read
View the most recent cur-
rent value monitored by
the current transformer.
-1,999.000 to 9,999.000
- - - -
1080
[offset 50]
0x73
(115)
1 to 4
1
- - - -
15001
float
R
[`C;Er]
[ C.Er]
Current (1 to 4)
Error
View the cause of the
most recent load fault.
[nonE]
None (61)
[Shrt]
Shorted (127)
[open]
Open (65)
- - - -
1082
[offset 50]
0x73
(115)
1 to 4
2
- - - -
15002
uint
R
[`h;Er]
[ h.Er]
Current (1 to 4)
Heater Error
View the cause of the
most recent load fault
monitored by the current
transformer.
[nonE]
None (61)
[high]
High (37)
[Low]
Low (53)
- - - -
1084
[offset 50]
0x73
(115)
1 to 4
3
- - - -
15003
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E: EE-
PROM
S: User
Set