RME Specifications

Line Voltage/Power

• 20.4 to 30.8Vı (ac/dc), 50/60Hz, ±5 percent
• Power consumption: 7 W, 14VA
• Any external power supply used should comply with a class 2 or

SELV rating. (See specific module specification listing for maxi-

mum VA power consumption)

• Data retention upon power failure via nonvolatile memory
• Compliant with Semi F47-0200, Figure R1-1 voltage sag require-

ments

Environment

• 0 to 149°F (-18 to 65°C) operating temperature
• -40 to 185°F (-40 to 85°C) storage temperature
• 0 to 90 percent RH, non-condensing
• Rail Mount modules are considered to be open type equipment

needing to be installed in a fire and shock protection enclosure,

such as a NEMA Type 1 enclosure; unless all circuit connections

are Class 2 or SELV (Saftey Extra Low Voltage)

Agency Certifications

• UL®/EN 61010 listed; c-UL C22.2 #61010 File E185611 QUYX,

QUYX7

• ANSI/ISA 12.12.01-2007 Hazardous Locations Class 1, Div.

2-Group A, B, C, D Temperature code T4 (optional) File E184390

QUZW, QUZW7

• EN 60529 IP20; RM modules
• UL® 50, Type 4X indoor use, EN 60529 IP66; 1/16 DIN RUI,

NEMA 4X

• RoHS by design, W.E.E.E.
• CE

Serial Communications

• The RME module ships with the isolated Standard Bus protocol

for configuration and communication connection to all other EZ-

ZONE products

Maximum System Configuration

• One access module plus up to 16 additional RM modules (any

combination), with up to 152 control loops

Mounting

• DIN-rail specification EN50022, 35 x 7.5 mm (1.38 x 0.30 in.)
• Can be DIN-rail mounted or chassis mounted with customer-

supplied fasteners

Dimensions

Weight

155.0 mm

(6.10 in)

116.08 mm

(4.57 in)

Controller:

453.59 g (16 oz.)

Wiring Termination—Touch Safe Terminals

• Right angle and Front screw type terminal blocks (slots A, B, D,

E)

- Input, power and controller output terminals, touch safe re

movable 12 to 30 AWG

- Wire strip length 7.6 mm (0.30 in.)
- Torque 0.8Nm (7.0 lb.-in.) right angle, 0.5Nm (4.51 lb-in) front

terminal block

• Ring lug terminal block
- Wire strip length 7.6 mm (0.30 in.)
- Torque 1.13Nm (10.0 lb.-in.)
• Use solid or stranded copper conductors only

Connector

Dimension “A” (mm/in.)

Standard

148 (5.80)

Straight

155 (6.10)

Ring Terminal

166 (6.50)

Digital Input

• Update rate 10Hz
• DC voltage
- Max. input 36V at 3mA
- Min. high state 3V at 0.25mA
- Max. low state 2V

Dry Contact

• Update rate 10Hz
• Min. open resistance 100KΩ
• Max. closed resistance 50Ω

Output Hardware
Digital Output

• Update rate 10Hz
• Switched DC
- Output voltage 20VÎ (dc) or 12VÎ (dc), user selectable
- Max. supply current source 40mA at 20VÎ (dc) and 80mA at

12VÎ (dc)

• Open Collector
- Switched voltage max.: 32VÎ (dc)
- Max. switched current per output: 1.5A
- Max. switched current for all 6 outputs combined: 8A

Dual Solid-State Relays

• Dual SSR board option, Form A, 10A max. each SSRs combined

@ 24VÅ (ac) min., 264VÅ (ac) max., opto-isolated, without con-

tact suppression

- Maximum resistive load 10 A per output @ 240V (ac)
- Maximum 20 A per card @ 50

0

C

- Maximum 12 A per card @ 65

0

C

Quad Relays

• Four electromechanical relays, Form A, 5A, 24 to 240VÅ (ac) or

30VÎ (dc) max., resistive load, 100,000 cycles at rated load. Re-

quires a min. load of 20mA at 24V, 120/240 VÅ (ac) 125VA, 24VÅ

(ac) 25VA pilot duty

Process/Retransmit Outputs, Range Selectable

• - 0 to 10V Î(dc) into a min. 4KΩ load
- 0 to 20mA into max. 400Ω load
Resolution
- dc ranges: 0.2mV nominal
- mA ranges: 0.4µA nominal
Calibration Accuracy
- dc ranges: ±15 mV
- mA ranges: ±30 µA
Temperature Stability
- 100 ppm FSR/°C

Quad Solid-State Relays

• 2 A at 20 to 264VÅ (ac) maximum resistive load
• 50 VA 120/240VÅ (ac) pilot duty

Programmable Application Blocks

Actions (events) 8 total
Alarms 8 total
Compare 8 total
Off, greater than, less than, equal, not equal, greater than or

equal, less than or equal

Counters 8 total
Counts up or down, loads predetermined value on load signal.

Output is active when count value equals predetermined target

value.

Logic 8 total
Off, and, nand, or, nor, equal, not equal, latch
Linearization 8 total
Interpolated or stepped relationship