beautypg.com

Security function, Special output function, Security function block overview – Watlow EZ-ZONE RME User Manual

Page 108

background image

Watlow EZ-ZONE

®

RME Module

105

Chapter 6 Features

Security Function

Note:

Set on a Zone by Zone basis. This is independent of

the RUI Security Setting.

If the Password is enabled, the user must enter the

Password to get to menus that have been blocked due

to lock level settings. Rolling passwords require a

new password each time the power has been cycled to

the controller. It will be different for every controller.

The administrator password is required to change

the security settings even if the user enters their

password to override the security settings.

Security Function Block

Overview

Instances - 1 per RME

[LoC;o]

Operations Page : 1 to 3

[r;LoC]

Read Lock : 1 to 5

[S;LoC]

Write Security: 1 to 5

[LoC;P]

Profiling Page : 1 to 3

[PAS;E]

Password Enable : Off, On

[LoC;L]

Locked Access Level : 1 to 5

[roL;L]

Rolling Password : Off, On

[PAS;u]

User Password : 10 to 999

[PAS;A]

Administrator Password : 10 to 999

[CodE]

Public Key : xxx

[PASS]

Password : xxx

Write Security

Locked

Access Level

Rolling P

assword

User P

assword

Administrator P

assword

Publi

c Key

Password

Profiling P

age

Read Loc

k

Operations P

age

[`LoC]

Lock Menu

[FAct]

Factory Page

[ULoC]

Unlock Menu

[FAct]

Factory Page

Special Output Function

This function is used to configure outputs when used

with compressors, motorized valves or sequencers.
An error (1 - 4), when read, can indicate any of the

following: None, Open, Shorted, Measurement Error,

Bad Cal Data, Ambient Error, RTD Error, Fail, Math

Error, Not Sourced, Stale

Special Output

Overview

Instances - 4 per RME

[SFn;A]

Source Function A : None, Analog Input, Cool Power,

Heat Power, Power, Linearization, Math, Process

Value, Special Function Output 1, Variable

[SFn;b]

Source Function B : None, Cool Power, Heat Power,

Power, Linearization, Math, Variable

[`S2;A]

Source Zone A : 0 to 16

[`S2;b]

Source Zone B : 0 to 16

[Pon;A]

Power On Level 1 : -100.0 to 100.0 %

[Pon;b]

Power On Level 2 : -100.0 to 100.0 %

[PoF;A]

Power Off Level 1 : -100.0 to 100.0 %

[PoF;b]

Power Off Level 2 : -100.0 to 100.0 %

[`on;t]

Minimum On Time : 0 to 9,999 seconds

[`oF;t]

Minimum Off Time : 0 to 9,999 seconds

[``t;t]

Valve Travel Time : 10 to 9,999 seconds

[``db]

Dead Band : 1.0 to 100.0 %

[`o;S1]

Output 1 Size : 0 to 9,999

[`o;S2]

Output 2 Size : 0 to 9,999

[`o;S3]

Output 3 Size : 0 to 9,999

[`o;S4]

Output 4 Size : 0 to 9,999

[`t;dL]

Time Delay : 0 to 9,999 seconds

[`ot;o]

Output Order : Linear, Progressive

[`Si;A]

Source Instance A : 1 to 250

[``Fn]

Function : Off, Compressor, Motorized Valve, Sequencer

[`Si;b]

Source Instance B : 1 to 250

Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B

[`Su;A]

Source Value A : -1,999.000 to 9,999.000

[`Su;b]

Source Value B : -1,999.000 to 9,999.000

Power On Level

1

Power On Level

2

Power Off Level

1

Power Off Level

2

Minimum On

Time

Minimum Off

Tim

e

Valve

Trav

el Time

Dead Band

Output 1 Size

Output 2 Size

Output 3 Size

Output 4 Size

Time Dela

y

Output Orde

r

Functio

n

[`o;u1]

Output Value 1 : -1,999.000 to 9,999.000 %

[`o;u2]

Output Value 2 : -1,999.000 to 9,999.000 %

[`o;u3]

Output Value 3 : -1,999.000 to 9,999.000 %

[`o;u4]

Output Value 4 : -1,999.000 to 9,999.000 %

[`SoF]

Special Output Function Menu

[`SEt]

Setup Page

Output Value 4

Output Value 3

Output Value 2

Output Value 1

Error 1 to 4

Source Value A
Source Value B

[`SoF]

Special Output Function Menu

[oPEr]

Operation Page