beautypg.com

Process alarms, Alarm set points, Alarm hysteresis – Watlow EZ-ZONE RME User Manual

Page 87: Alarm latching, Alarm silencing

background image

Watlow EZ-ZONE

®

RME Module

84

Chapter 6 Features

Process Alarms

A process alarm uses one or two absolute set points

to define an alarm condition.

Select the alarm type [`A;ty] via the Setup Page,

Alarm Menu.

Alarm Set Points

The alarm high set point defines the process value

or temperature that will trigger a high side alarm.

The alarm low set point defines the temperature that

will trigger a low side alarm. For deviation alarms,

a negative set point represents a value below closed

loop set point. A positive set point represents a value

above closed loop set point. View or change alarm set

points with Alarm Low [`A;Lo] and Alarm High Set

Points [`A;hi] (Operations Page, Alarm Menu).

Alarm Hysteresis

An alarm state is triggered when the process value

reaches the alarm high or alarm low set point. Alarm

Hysteresis defines how far the process must return

into the normal operating range before the alarm can

be cleared.

Alarm Hysteresis is a zone inside each alarm set

point. This zone is defined by adding the hysteresis

value to the alarm low set point or subtracting the

hysteresis value from the alarm high set point. View

or change Alarm Hysteresis [`A;hy] via the Setup

Page, Alarm Menu.

Normal Operating Range

Low Side Alarm Range

High Side Alarm Range

Alarm High Set Point

Alarm Low Set Point

Time

Temperature

Alarm Set Points and Hysteresis

Alarm Hysteresis

Alarm Hysteresis

Alarm Latching

A latched alarm will remain active after the alarm

condition has passed. It can only be deactivated by

the user and only when the alarm condition no longer

exists.

If using an RUI an active message, such as an

alarm message, will cause the display to toggle be-

tween the normal settings and the active message in

the upper display and [Attn] in the lower display. To

clear a latched alarm:
1. Push the Advance Key

to display [ignr] in the

upper display and the message source in the lower

display.

2. Use the Up ¿ or Down ¯ keys to scroll through

possible responses, such as Clear [`CLr] or Silence
[`SiL]

.

3. Push the Advance

or Infinity ˆ key to execute

the action.

Without an RUI, a latched alarm can be reset by

cycling power to the module or configuring an Ac-

tion function within the control to perform a reset.

Do this by setting the Action Function to alarm and

trigger the Action to occur through Source Function

A.
An alarm that is not latched (self-clearing) will de-

activate automatically when the alarm condition has

passed. Turn Alarm Latching [`A;LA] on or off via

the Setup Page, Alarm Menu.

Normal Operating Range

Alarm High

Set Point

Time

Temperature

Alarm Low

Set Point

Alarm Response with Hysteresis

The alarm state continues until the

temperature drops to the Alarm High

Set Point minus the hysteresis. A

latching alarm could be turned off by

the operator at this point. A

non-latching alarm would turn off

automatically.

The alarm state begins when the temperature

reaches the Alarm High Set Point

Process

Temperature

Alarm Hysteresis

Alarm Silencing

If alarm silencing is on the operator can disable the

alarm output while the controller is in an alarm

state. The process value or temperature has to enter

the normal operating range beyond the hysteresis

zone to activate the alarm output function again.

If using an RUI an active message, such as an

alarm message, will cause the display to toggle be-

tween the normal settings and the active message in

the upper display and [Attn] in the lower display. To

silence an alarm:
1. Push the Advance Key

to display [ignr] in the

upper display and the message source in the lower

display.

2. Use the Up ¿ and Down ¯ keys to scroll through

possible responses, such as Clear [`CLr] or Silence
[`SiL]

.

3. Push the Advance

or Infinity ˆ key to execute

the action.

Without an RUI, silencing aa alarm can be accom-

plished by configuring an Action function within the

control to silence the alarm. Do this by setting the

Action Function to Silence and trigger the Action to

occur through Source Function A.

Turn Alarm Silencing [`A;Si] on or off via the

Setup Page, Alarm Menu.