Security setting menu, Diagnostics menu, Security setting menu diagnostics menu – Watlow EZ-ZONE RME User Manual
Page 83

Watlow EZ-ZONE
®
RME Module
•
80
•
Chapter 5 Factory Page
Expansion Module
•
Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
& Read/
Write
[pas;a]
[PAS.A]
Security Setting
Administrator Password
Applies if Password Enable is
ON. Used to acquire access to
menus made available through
the Locked Access Level setting.
Do not forget the password as
it is required to change Locked
Access Level, Read Lock, Write
Security and the ability to change
the Passwords.
10 to 999
156
- - - -
- - - -
- - - -
- - - -
- - - -
[ULoC]
[FCty]
Security Setting Menu
[Code]
[CodE]
Security Setting
Public Key
If Rolling Password turned on,
generates a random number
when power is cycled. If Rolling
Password is off, fixed number will
be displayed.
Customer Specific
0
- - - -
- - - -
- - - -
- - - -
- - - -
[pass]
[PASS]
Security Setting
Password
Number returned from calcula-
tion found in Features section
under Password Security.
-1999 to 9999
0
- - - -
- - - -
- - - -
- - - -
- - - -
[diAg]
[FCty]
Diagnostics Menu
[``Pn]
[ Pn]
Diagnostics Menu
Part Number
Display this controller's part
number.
24
- - - -
- - - -
0x65
(101)
1
9
115
1009
int
RWE
[`rEu]
[ rEu]
Diagnostics Menu
Software Revision
Display this controller's firmware
revision number.
5
- - - -
4
0x65
(101)
1 to 5
0x11 (17)
116
1003
int
R
[S;bLd]
[S.bLd]
Diagnostics Menu
Software Build Number
Display the firmware build num-
ber.
0 to 2,147,483,647
- - - -
8
0x65
(101)
1 to 5
5
- - - -
1005
float
R
[``Sn]
[ Sn]
Diagnostics Menu
Serial Number
Display the serial number.
0 to 2,147,483,647
- - - -
12
0x65
(101)
1
7
- - - -
1007
float
RWE
[dAtE]
[dAtE]
Diagnostics Menu
Date of Manufacture
Display the date code. Date code
format is YYWW, where YY is
last two digits of the year, and
WW is the week of the year.
0 to 2,147,483,647
- - - -
14
0x65
(101)
1
8
- - - -
1008
float
RWE
No Dis-
play
Diagnostics Menu
Hardware ID
Read the hardware ID.
24 or 117
24
0
0x65
(101)
1
1
- - - -
1001
signed
32-bit
R
Note: Some values will be rounded off to fit in the four-character display . Full values can
be read with another interface .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set