beautypg.com

Math menu – Watlow EZ-ZONE RME User Manual

Page 39

background image

Watlow EZ-ZONE

®

RME Module

36

Chapter 3 Operations Page

RME Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

&

Read/

Write

[`Su;g]
[ Su.g]

Logic (1 to 8)

Source Value G

View the value of Source

G.

[`off]

Off (62)

[``on]

On (63)

- - - -

3080
[off 80]

0x7F

(127)

1 to 8

0x1F (31)

- - - -

27031

uint
R

[`Su;h]
[ Su.h]

Logic (1 to 8)

Source Value H

View the value of Source

H.

[`off]

Off (62)

[``on]

On (63)

- - - -

3082
[off 80]

0x7F

(127)

1 to 8

0x20 (32)

- - - -

27032

uint
R

[``o;u]
[ o.v]

Logic (1 to 8)

Output Value

View the value of this

function's output.

[`off]

Off (62)

[``on]

On (63)

- - - -

3086
[off 80]

0x7F

(127)

1 to 8

0x22 (34)

- - - -

27034

uint
R

No Dis-

play

Logic (1 to 8)

Error

Read reported cause for

logic error

None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)

- - - -

3090
[offset 80]

0x7F

(127)

1 to 4

0x24 (36)

- - - -

27036

uint

R

[MAt]
[oPEr]
Math Menu

[`Su;A]
[ Su.A]

Math (1 to 8)

Source Value A

View the value of Source

A.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

2210
[off 70]

0x7D

(125)

1 to 8

0x10 (16)

- - - -

25016

float
R

[`Su;b]
[ Su.b]

Math (1 to 8)

Source Value B

View the value of Source

B.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

2212
[off 70]

0x7D

(125)

1 to 8

0x11 (17)

- - - -

25017

float
R

[`Su;C]
[ Su.C]

Math (1 to 8)

Source Value C

View the value of Source

C.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

2214
[off 70]

0x7D

(125)

1 to 8

0x12 (18)

- - - -

25018

float
R

[`Su;d]
[ Su.d]

Math (1 to 8)

Source Value D

View the value of Source

D.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

2216
[off 70]

0x7D

(125)

1 to 8

0x13 (19)

- - - -

25019

float
R

[`Su;E]
[ Su.E]

Math (1 to 8)

Source Value E

View the value of Source

E.

[`off]

Off (62)

[``on]

On (63)

- - - -

2218
[off 70]

0x7D

(125)

1 to 8

0x14 (20)

- - - -

25020

uint
R

[oFSt]
[oFSt]

Math (1 to 8)

Offset

Set an offset to be applied

to this function's output.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

0

2224
[off 70]

0x7D

(125)

1 to 8

0x17 (23)

- - - -

25023

float
RWES

Note:

Some values will be rounded off to fit in the four-character display . Full values can be

read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E: EE-

PROM

S: User

Set