beautypg.com

Current loop output adjustment – Teledyne GFC-7000T - Trace CO2 Analyzer - manual User Manual

Page 149

background image

Operating Instructions

Model GFC7000TA Carbon Dioxide Analyzer

Teledyne Analytical Instruments

131

Press SET> to select the analog output channel to be

configured:

DISPLAYED

AS

=

CHANNEL

CONC_OUT_1

=

A1

CONC_OUT_2

=

A2

TEST

OUTPUT

=

A4

DIAG

ANALOG I / O CONFIGURATION

PREV

NEXT

ENTR

EXIT

DIAG AIO

AOUTS CALIBRATED:

NO

< SET

SET>

CAL

EXIT

FROM ANALOG I/O CONFIGURATION MENU

DIAG AIO

CONC_OUT_1 :5V, NO CAL

< SET SET>

EDIT

EXIT

DIAG AIO

CONC_OUT_1 CALIBRATED: YES

< SET

CAL

EXIT

DIAG AIO

CONC_OUT_1 RANGE: 5V

SET>

EDIT

EXIT

DIAG AIO

CONC_OUT_2 CALIBRATED: NO

< SET

CAL

EXIT

DIAG AIO

CONC_OUT_1 VOLT–Z : 0 mV

U100 UP10 UP DOWN DN10 D100

ENTR EXIT

Press to increase / decrease the analog output

by 100, 10 or 1 counts.

Continue adjustments until the voltage measured

at the output of the analyzer and/or the input of

the recording device matches the value in the

upper right hand corner of the display to the

tolerance listed in Table 6-20.

The concentration display will not change. Only

the voltage reading of your voltmeter will change.

DIAG AIO

CONC_OUT_1 VOLT–S : 4500 mV

U100 UP10 UP DOWN DN10 D100

ENTR EXIT

DIAG AIO

CONC_OUT_1 REC OFS: 0 mV

< SET

SET>

EDIT

EXIT

If AutoCal is ON, go to

Section 6.7.3

EXIT

ignores the

new setting.

ENTR

accepts the

new setting.

DIAG AIO

CONC_OUT_1 AUTO CAL: OFF

< SET

SET>

EDIT

EXIT

6.13.4.4. Current Loop Output Adjustment

A current loop option is available and can be installed as a retrofit for each of the analog outputs of the
analyzer (s 5.2). This option converts the DC voltage analog output to a current signal with 0-20 mA
output current. The outputs can be scaled to any set of limits within that 0-20 mA range. However, most
current loop applications call for either 2-20 mA or 4-20 mA range. All current loop outputs have a +5%
over-range. Ranges with the lower limit set to more than 1 mA (e.g., 2-20 or 4-20 mA) also have a -5%
under-range.

To switch an analog output from voltage to current loop after installing the current output printed circuit
assembly, follow the instructions in Section 6.13.4.4 and select CURR from the list of options on the
RANGE menu.

Adjusting the signal zero and span values of the current loop output is done by raising or lowering the
voltage of the respective analog output. This proportionally raises or lowers the current produced by the
current loop option.

Similar to the voltage calibration, the software allows this current adjustment to be made in 100, 10 or 1
count increments. Since the exact current increment per voltage count varies from output to output and
from instrument to instrument, you will need to measure the change in the current with a current meter
placed in series with the output circuit (Figure 6-16).