H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

H3-13: Analog Input Filter Time Constant

Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter prevents erratic drive control when using a “noisy” analog reference. Drive operation becomes more

stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog signals.

No.

Name

Setting Range

Default

H3-13

Analog Input Filter Time Constant

0.00 to 2.00 s

0.03 s

n

H3-14: Analog Input Terminal Enable Selection

When one of the multi-function digital input parameters is set for “Analog input enable” (H1-oo = C), the value set to H3-14

determines which analog input terminals are enabled and which terminals are disabled when the input is closed. All analog

input terminals will be enabled all of the time if H1-oo is not set to C.

No.

Name

Setting Range

Default

H3-14

Analog Input Terminal Enable Selection

1 to 3

2

Setting 1: A1 Only Enabled
Setting 2: A2 Only Enabled
Setting 3: Terminals A1 and A2

n

H3-16 and H3-17: Terminal A1/A2 Offset

Set the offset level of the selected input value to terminals A1 or A2 that is equal to 0 Vdc input. These parameters rarely

require adjustment.

No.

Name

Setting Range

Default

H3-16

Terminal A1 Offset

-500 to 500

0

H3-17

Terminal A2 Offset

-500 to 500

0

n

Multi-Function Analog Input Terminal Settings

See

Table 1.30

for information on how H3-02 and H3-10 determine functions for terminals A1 and A2.

Note:

The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting

and adjusting analog input functions.

Table 1.30 Multi-Function Analog Input Terminal Settings

Setting

Function

Page

0

Frequency Bias

95

1

Frequency Gain

95

2

Auxiliary Frequency Reference 1

95

3

Auxiliary Frequency Reference 2

95

4

Output Voltage Bias

95

5

Accel/Decel Time Gain

95

6

DC Injection Braking Current

95

7

Overtorque/Undertorque Detection Level

96

8

Stall Prevention Level During Run

96

Setting

Function

Page

9

Output Frequency Lower Limit Level

96

B

PI Feedback

96

C

PI Setpoint

96

D

Frequency Bias

96

E

Motor Temperature (PTC Input)

96

F

Through Mode

96

16

Differential PI Feedback

96

25

Secondary PI Setpoint

26

Secondary PI Feedback

1.7 H: Terminal Functions

94