n

RS-422 Interface

R–
R+
S–
S+

IG

PLC

Drive

Drive

Drive

S–
S+
R–
R+
IG

S–
S+
R–
R+
IG

S–
S+
R–
R+
IG

S2

OFF

S2

OFF

S2

ON

Figure E.4 RS-422 Interface

Note:

1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other

slave devices.

2. Set H5-07 to 1 when using the RS-422 interface in a multi-drop circuit.

Set H5-07 to 0 when using the RS-422 interface in a point-to-point circuit.

u

Network Termination

The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination resistor that

can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the termination resistor

by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not located at the network

line end.

E.3 Connecting to a Network

306

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual