Defaults by drive model, A.18 defaults by drive model, Board – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual
Page 241

A.18 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table A.7 600 V Class Drives Default Settings by Drive Model
No.
Name
Unit
–
Model
–
5A0003
5A0004
5A0006
5A0009
5A0011
o2-04
Drive Model Selection
Hex.
C3
C4
C5
C7
E2-11
Motor Rated Power
kW
(HP)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
494.4
415.3
320.2
239.95
199.86
C6-02
Carrier Frequency Selection
–
7
7
7
7
7
E2-01
Motor Rated Current
A
2.7
3.9
6.1
9
11
E2-02
Motor Rated Slip
Hz
2.5
3.0
2.7
1.5
1.3
E2-03
Motor No-Load Current
A
0.8
1.2
1.8
2.7
3.3
E2-05
Motor Line-to-Line Resistance
Ω
13.72
8.825
4.936
2.601
1.446
E2-10
Motor Iron Loss for Torque Compensation
W
53
77
130
193
263
L2-02
Momentary Power Loss Ride-Thru Time
s
0.2
0.3
0.5
0.5
0.8
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.5
0.5
0.8
0.8
1
L2-04
Momentary Power Loss Voltage Recovery
Time
s
0.5
0.5
0.6
0.7
0.8
L3-24
Motor Acceleration Time for Inertia
Calculations
s
0.166
0.145
0.154
0.168
0.175
L8-02
Overheat Alarm Level
°C
110
110
110
110
115
L8-35
Installation Method Selection
–
2
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
No.
Name
Unit
Default Settings
–
Model
–
5A0017
5A0022
5A0027
5A0032
o2-04
Drive Model Selection
Hex.
CA
CC
CD
CE
E2-11
Motor Rated Power
kW (HP)
11
(15)
15
(20)
18.5
(25)
22
(30)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
172
154
140
129
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
17
22
27
32
E2-02
Motor Rated Slip
Hz
1.7
1.6
1.67
1.7
E2-03
Motor No-Load Current
A
5.1
6.6
8.1
9.6
E2-05
Motor Line-to-Line Resistance
Ω
1.17
0.9
0.66
0.52
E2-10
Motor Iron Loss for Torque Compensation
W
385
440
508
586
L2-02
Momentary Power Loss Ride-Thru Time
s
1
2
2
2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1
1.2
1.2
1.2
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.9
1
1
1
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.27
0.24
0.32
0.36
L8-02
Overheat Alarm Level
°C
120
120
115
115
L8-35
Installation Method Selection
–
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
A.18 Defaults by Drive Model
YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual
241
A