beautypg.com

Defaults by drive model, A.18 defaults by drive model, Board – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 241

background image

A.18 Defaults by Drive Model

The following tables show parameters and default settings that change with the drive model selection (o2-04).

Table A.7 600 V Class Drives Default Settings by Drive Model

No.

Name

Unit

Model

5A0003

5A0004

5A0006

5A0009

5A0011

o2-04

Drive Model Selection

Hex.

C3

C4

C5

C7

E2-11

Motor Rated Power

kW

(HP)

1.5

(2)

2.2

(3)

3.7

(5)

5.5

(7.5)

7.5

(10)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

0.5

b8-04

Energy Saving Coefficient Value

494.4

415.3

320.2

239.95

199.86

C6-02

Carrier Frequency Selection

7

7

7

7

7

E2-01

Motor Rated Current

A

2.7

3.9

6.1

9

11

E2-02

Motor Rated Slip

Hz

2.5

3.0

2.7

1.5

1.3

E2-03

Motor No-Load Current

A

0.8

1.2

1.8

2.7

3.3

E2-05

Motor Line-to-Line Resistance

Ω

13.72

8.825

4.936

2.601

1.446

E2-10

Motor Iron Loss for Torque Compensation

W

53

77

130

193

263

L2-02

Momentary Power Loss Ride-Thru Time

s

0.2

0.3

0.5

0.5

0.8

L2-03

Momentary Power Loss Minimum Baseblock

Time

s

0.5

0.5

0.8

0.8

1

L2-04

Momentary Power Loss Voltage Recovery

Time

s

0.5

0.5

0.6

0.7

0.8

L3-24

Motor Acceleration Time for Inertia

Calculations

s

0.166

0.145

0.154

0.168

0.175

L8-02

Overheat Alarm Level

°C

110

110

110

110

115

L8-35

Installation Method Selection

2

2

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

No.

Name

Unit

Default Settings

Model

5A0017

5A0022

5A0027

5A0032

o2-04

Drive Model Selection

Hex.

CA

CC

CD

CE

E2-11

Motor Rated Power

kW (HP)

11

(15)

15

(20)

18.5

(25)

22

(30)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b8-04

Energy Saving Coefficient Value

172

154

140

129

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

17

22

27

32

E2-02

Motor Rated Slip

Hz

1.7

1.6

1.67

1.7

E2-03

Motor No-Load Current

A

5.1

6.6

8.1

9.6

E2-05

Motor Line-to-Line Resistance

Ω

1.17

0.9

0.66

0.52

E2-10

Motor Iron Loss for Torque Compensation

W

385

440

508

586

L2-02

Momentary Power Loss Ride-Thru Time

s

1

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1

1.2

1.2

1.2

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.9

1

1

1

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.27

0.24

0.32

0.36

L8-02

Overheat Alarm Level

°C

120

120

115

115

L8-35

Installation Method Selection

2

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

A.18 Defaults by Drive Model

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

241

A

Parameter List