B2: dc injection braking and short circuit braking, Braking depending on the selected control mode – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 29

background image

Setting 0: Standard
Setting 1: Switch Phase Order

The direction of the motor is reversed.

n

b1-17: Run Command at Power Up

Determines whether an external Run command that is active during power up will start the drive.

No.

Parameter Name

Setting Range

Default

b1-17

Run Command at Power Up

0, 1

1

Setting 0: Disregarded

A new Run command must be issued after power up. Cycle the Run command to start the drive.

Note:

For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued at

power up, the RUN indicator LED will flash quickly.

Setting 1: Allowed

The motor will start immediately after a power up if a Run command is already enabled.

WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin

rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to

powering up the drive. Failure to comply may cause serious injury.

u

b2: DC Injection Braking and Short Circuit Braking

These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.

n

b2-01: DC Injection Braking Start Frequency

Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).

No.

Name

Setting Range

Default

b2-01

DC Injection Braking Start Frequency

0.0 to 10.0 Hz

Determined by

A1-02

The function triggered by parameter b2-01 depends on the control mode that has been selected.

V/f (A1-02 = 0)

For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output

frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.

Output

frequency

Time

b2-04

DC Injection

Braking

E1-09 Min. Frequency
b2-01 Zero Speed Level

Figure 1.8 DC Injection Braking at Stop for V/f

Note:

If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency

falls to the value set to E1-09.

OLV/PM (A1-02 = 5)

For these control modes, parameter b2-01 sets the starting frequency for Short-Circuit Braking at stop. When the output

frequency falls below the setting of b2-01, Short-Circuit Braking is enabled for the time set in parameter b2-13. If DC Injection

Braking time is enabled at stop, then DC Injection Braking is performed for the time set in b2-04 after Short-Circuit Braking

is complete.

1.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

29

1

Parameter Details