1.7 H: Terminal Functions

H parameters assign functions to the external terminals.

u

H1: Multi-Function Digital Inputs

n

H1-01 to H1-07: Functions for Terminals S1 to S7

These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in

Table

1.28

.

No.

Parameter Name

Setting

Range

Default

H1-01

Multi-Function Digital Input Terminal S1 Function Selection

1 to B2

40 (F)

<1>

: Forward Run Command (2-Wire sequence)

H1-02

Multi-Function Digital Input Terminal S2 Function Selection

1 to B2

41 (F)

<1>

: Reverse Run Command (2-Wire sequence)

H1-03

Multi-Function Digital Input Terminal S3 Function Selection

0 to B2

24: External Fault

H1-04

Multi-Function Digital Input Terminal S4 Function Selection

0 to B2

14: Fault Reset

H1-05

Multi-Function Digital Input Terminal S5 Function Selection

0 to B2

3 (0)

<1>

: Multi-Step Speed Reference 1

H1-06

Multi-Function Digital Input Terminal S6 Function Selection

0 to B2

4 (3)

<1>

: Multi-Step Speed Reference 2

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

0 to B2

6 (4)

<1>

: Jog Reference Selection

<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.

Table 1.28 Multi-Function Digital Input Terminal Settings

Setting

Function

Page

0

3-Wire Sequence

73

3

Multi-Step Speed Reference 1

73

4

Multi-Step Speed Reference 2

6

Jog reference Selection

73

7

Accel/Decel Time Selection 1

74

8

Baseblock Command (N.O.)

74

9

Baseblock Command (N.C.)

A

Accel/Decel Ramp Hold

74

B

Drive Overheat Alarm (oH2)

74

C

Analog Terminal Input Selection

74

F

Through Mode

74

10

Up Command

75

11

Down Command

12

Forward Jog

76

13

Reverse Jog

14

Fault Reset

76

15

Fast Stop (N.O.)

76

17

Fast Stop (N.C.)

76

18

Timer Function Input

76

19

PID Disable

77

1B

Program Lockout

77

1E

Reference Sample Hold

77

20 to 2F External Fault

77

30

PID Integral Reset

78

31

PID Integral Hold

78

34

PID Soft Starter Cancel

78

35

PID Input Level Selection

78

40

Forward Run Command (2-Wire sequence)

78

41

Reverse Run Command (2-Wire sequence)

Setting

Function

Page

42

Run Command (2-Wire sequence 2)

78

43

FWD/REV Command (2-Wire sequence 2)

44

Offset Frequency 1

79

45

Offset Frequency 2

46

Offset Frequency 3

47

Node Setup

79

49

GF1 Error (N.O., N.C.)

79

4A

50

Motor Pre-Heat 2

79

51

Sequence Timer Disable

79

52

Sequence Timer Cancel

79

60

Motor Pre-Heat 1

79

61

External Speed Search Command 1

79

62

External Speed Search Command 2

79

63

Field Weakening

79

65

KEB Ride-Thru 1 (N.C.)

80

66

KEB Ride-Thru 1 (N.O.)

67

Communications Test Mode

80

68

High Slip Braking

80

69

Jog 2

80

6A

Drive Enabled

80

6D

AUTO Mode Select

80

6E

HAND Mode Select

80

70

Drive Enable2

81

7A

KEB Ride-Thru 2 (N.C.)

81

7B

KEB Ride-Thru 2 (N.O.)

7C

Short Circuit Braking (N.O.)

81

7D

Short Circuit Braking (N.C.)

A4

BP Emergency Override

81

A5

BP Drive/Bypass Selection

81

1.7 H: Terminal Functions

72