L8-40: Carrier Frequency Reduction Off-Delay Time

Sets a hold time before returning to the original carrier frequency setting after the carrier frequency has been temporarily

derated as determined by L8-38. The carrier frequency reduction function is disabled when this value is 0.00 s.

No.

Name

Setting Range

Default

L8-40

Carrier Frequency Reduction Off-Delay Time

0.00 to 2.00 s

0.50 s

n

L8-41: High Current Alarm Selection

Triggers a high current alarm (HCA) when the output current exceeds 150% of the drive rated current.

No.

Name

Setting Range

Default

L8-41

High Current Alarm Selection

0, 1

0

Setting 0: Disabled

No alarm is detected.

Setting 1: Enabled

An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm

(H2-oo = 10) will close.

n

L8-55: Internal Braking Transistor Protection

Enables and disables protection for the internal braking transistor.

No.

Name

Setting Range

Default

L8-55

Internal Braking Transistor Protection

0, 1

1

Setting 0: Disabled

Disable braking transistor protection when not using the internal braking transistor, including the following instances:
• When using a regen converter such as DC5.
• When using a regen unit such as RC5.
• When using external braking transistor options like CDBR units.
• When using the drive in common DC bus applications and the internal braking unit is not installed.
Enabling L8-55 under such conditions can incorrectly trigger a braking transistor fault (rr).

Setting 1: Enabled

Enable L8-55 when connecting a braking resistor or a braking resistor unit to the drive built-in braking transistor.
Models 5A0003 to 5A0052 come with a built-in braking transistor.

n

L8-97: Carrier Frequency Reduction Rate during oH Pre-Alarm

Derates the carrier frequency to the level set to L8-39 during oH pre-alarm.

No.

Name

Setting Range

Default

L8-97

Carrier Frequency Reduction Rate during oH Pre-Alarm

0, 1

0

Setting 0: Disabled
Setting 1: Enabled