A.16 Control Mode Dependent Parameter Default Values

The tables below list parameters that depend on the control mode selection. Changing the control mode initializes these

parameters to the values shown here.

u

A1-02 (Motor Control Mode) Dependent Parameters

Table A.3 A1-02 (Motor Control Mode) Dependent Parameters and Default Values

No.

Name

Setting Range

Resolution

Control Modes (A1-02)

V/f (0)

OLV/PM (5)

b3-08

Current Control Gain during Speed Search (Speed

Estimation Type)

0.00 to 6.00

0.01

<1>

0.30

C2-01

S-Curve Characteristic at Accel Start

0.00 to 10.00

0.01 s

0.20

1.00

C4-01

Torque Compensation Gain

0.00 to 2.50

0.01

1.00

0.00

C4-02

Torque Compensation Primary Delay Time

0 to 60000

1 ms

200

100

C6-02

Carrier Frequency Selection

1 to 9; A to F

1

<1>

2

E1-04

Maximum Output Frequency

40.0 to 240.0

0.1 Hz

<2>

60.0

E1-05

Maximum Voltage

0.0 to 733.1

0.1 V

<2>

200.0

E1-06

Base Frequency

0.0 to 240.0

0.1 Hz

<2>

60.0

E1-09

Minimum Output Frequency

0.0 to 240.0

0.1 Hz

<2>

3.0

L1-01

Motor Overload Protection Selection

0, 1, 4

1

1

4

L3-20

DC Bus Voltage Adjustment Gain

0.00 to 5.00

0.01

1.00

0.65

L8-38

Carrier Frequency Reduction Selection

0 to 2

1

<1>

0

L8-40

Carrier Frequency Reduction Off-Delay Time

0.00 to 2.00

0.01 s

0.50

0.00

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-03, V/f Pattern Selection.

A.16 Control Mode Dependent Parameter Default Values

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

239

A