Control mode dependent parameter default values, A1-02 (motor control mode) dependent parameters – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual
Page 239

A.16 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection. Changing the control mode initializes these
parameters to the values shown here.
u
A1-02 (Motor Control Mode) Dependent Parameters
Table A.3 A1-02 (Motor Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
OLV/PM (5)
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
0.00 to 6.00
0.01
<1>
0.30
C2-01
S-Curve Characteristic at Accel Start
0.00 to 10.00
0.01 s
0.20
1.00
C4-01
Torque Compensation Gain
0.00 to 2.50
0.01
1.00
0.00
C4-02
Torque Compensation Primary Delay Time
0 to 60000
1 ms
200
100
C6-02
Carrier Frequency Selection
1 to 9; A to F
1
<1>
2
E1-04
Maximum Output Frequency
40.0 to 240.0
0.1 Hz
<2>
60.0
E1-05
Maximum Voltage
0.0 to 733.1
0.1 V
<2>
200.0
E1-06
Base Frequency
0.0 to 240.0
0.1 Hz
<2>
60.0
E1-09
Minimum Output Frequency
0.0 to 240.0
0.1 Hz
<2>
3.0
L1-01
Motor Overload Protection Selection
0, 1, 4
1
1
4
L3-20
DC Bus Voltage Adjustment Gain
0.00 to 5.00
0.01
1.00
0.65
L8-38
Carrier Frequency Reduction Selection
0 to 2
1
<1>
0
L8-40
Carrier Frequency Reduction Off-Delay Time
0.00 to 2.00
0.01 s
0.50
0.00
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-03, V/f Pattern Selection.
A.16 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual
239
A
Parameter List