Table 1.32 HAND/AUTO Multi-Function Inputs, Legacy Behavior (S5-04 = 0)

AUTO Mode Selection

(H1-oo = 6D)

HAND Mode Selection

(H1-oo = 6E)

Frequency Reference

Run Command

Open

-

Based on S5-01

Based on b1-02

Closed

-

Based on b1-02

-

Open

Based on b1-02

-

Closed

Based on S5-01

If S5-04 is set to 0, the AUTO and HAND multi-function inputs (setting 6D and 6E) can only be used individually or an oPE03

error will occur.

AUTO

Fref via b1-01
Run via b1-02

HAND

Fref via S5-01

Run On

OFF

Fref via b1-01

Run Off

S5-02 = 1 AND

HAND key

S5-02 = 1 AND

AUTO key

OFF key

HAND key

OFF key AND o2-02 = 1

AUTO key

OR run command

Figure 1.83 Legacy Behavior (S5-04 = 0)

Setting 2: Normal Operation Mode with Memory

When switching AUTO/HAND modes from the HOA keypad, the drive will memorize the operation mode when the power

to the drive is shut off. This will be the initial operating mode when power is reapplied.
When switching AUTO/HAND modes from a Multi-Function Input, the drive will start with the Multi-Function Input setting.
HAND mode: The drive starts with the OFF mode when cycling the power to the drive.
AUTO mode: The drive starts with the AUTO mode when cycling the power to the drive.
OFF mode: The drive starts with the OFF mode when cycling the power to the drive.

n

S5-05: HAND Frequency Reference 1

Sets the frequency reference used in HAND mode when S5-01 is set to 3.

Note:

Setting units and range are determined by parameters o1-03, o1-10, and o1-11.

No.

Name

Setting Range

Default

S5-05

HAND Frequency Reference 1

0.00 to 240.00 Hz

0.00 Hz

n

S5-07: HAND Key Function Selection (HOA Keypad)

Determines whether the HAND key on the HOA keypad will be enabled for switching between HAND and AUTO.

No.

Name

Setting Range

Default

S5-07

HAND Key Function Selection (HOA Keypad)

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

1.11 S: Special Parameters