Register No.

Contents

00C1H

Fault Contents 4
bit 0

External Fault at input terminal S3 (EF3)

bit 1

External Fault at input terminal S4 (EF4)

bit 2

External Fault at input terminal S5 (EF5)

bit 3

External Fault at input terminal S6 (EF6)

bit 4

External Fault at input terminal S7 (EF7)

bit 5

Reserved

bit 6

Cooling Fan Error (FAn)

bit 7 to 9

Reserved

bit A

Input Phase Loss (PF)

bit B

Output Phase Loss (LF)

bit C

Motor Overheat (PTC input) (oH3)

bit D

Digital Operator Connection Fault (oPr)

bit E

EEPROM Write Error (Err)

bit F

Motor Overheat Fault (PTC input) (oH4)

00C2H

Fault Contents 5
bit 0

MEMOBUS/Modbus Communication Error (CE)

bit 1

Option Communication Error (bUS)

bit 2 to 5

Reserved

bit 6

Option External Fault (EF0)

bit 7

PI Feedback Loss (FbL)

bit 8

Undertorque Detection 1 (UL3)

bit 9

Reserved

bit A

High Slip Braking Overload (oL7)

bit B to E

Reserved

bit F

Hardware Fault (includes oFx)

00C3H

Fault Contents 6
bit 0 to 4

Reserved

bit 5

Current Imbalance (LF2)

bit 6

Pullout Detection (STo)

bit 7 to 9

Reserved

bit A

Too Many Speed Search Restarts (SEr)

bit B to F

Reserved

00C4H

Fault Contents 7
bit 0

PI Feedback Loss (FbH)

bit 1

External Fault 1, input terminal S1 (EF1)

bit 2

External Fault 2, input terminal S2 (EF2)

bit 3, bit 4

Reserved

bit 5

Current Offset Fault (CoF)

bit 6 to B

Reserved

bit C

Output Voltage Detection Fault (voF)

bit D to F

Reserved

00C5H

Fault Contents 8
bit 0

Reserved

bit 1

Node Setup Fault (nSE)

bit 2 to 5

Reserved

bit 9

Motor Underload Protection (UL6)

bit A to F

Reserved

00C6H, 00C7H

Reserved

E.9 MEMOBUS/Modbus Data Table

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

321

E

MEMOBUS/Modbus Communications