B8: energy saving, Fine-tuning pi, B8-01: energy saving control selection – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 49

background image

Setting 1: Reverse Enabled

Negative PI output will cause the drive to run in the opposite direction.

n

Fine-Tuning PI

Follow the directions below to fine tune PI control parameters:

Table 1.11 PI Fine Tuning

Goal

Tuning Procedure

Result

Suppress overshoot

Increase the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Achieve stability quickly while

allowing some overshoot

Decrease the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Suppress long cycle oscillations

(longer than the integral time setting) Increase the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Suppress short cycle oscillations

If oscillations are a problem, reduce the

proportional gain (b5-02) or increase the PI

primary delay time (b5-08)

Response

Before adjustment

After adjustment

Time

u

b8: Energy Saving

The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level.

Note:

1. Energy Saving is not designed for applications that experience instantaneous heavy loads or applications that rarely operate with light

load conditions.

2. Energy Saving is mainly designed for applications with variable torque, however Energy Saving is not appropriate for applications where

the load may suddenly increase.

3. The performance of the Energy Saving function depends on the accuracy of the motor data. Always perform Auto-Tuning and correctly

enter the motor data before using this function.

n

b8-01: Energy Saving Control Selection

Enables or disables the Energy Saving function.

No.

Parameter Name

Setting Range

Default

b8-01

Energy Saving Control Selection

0, 1

Determined by

A1-02

1.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

49

1

Parameter Details