C.1 APOGEE FLN Set-Up

A Yaskawa America, Inc. representative is responsible for proper configuration of the drive for the primary application, while

a Siemens Building Technologies, Inc. representative is responsible for field panel programming to make use of the drive

functionality in the building automation system. As such, there must be coordination between the Yaskawa America and

Siemens Building Technologies representatives to ensure that the programming of the drive is consistent with the particular

application requirements. After verifying that the drive installation and wiring are correct, apply power to the drive.

Table C.

1

lists the parameters and values required for proper APOGEE FLN communication and control.

Z1000 parameter settings For APOGEE FLN communications

Table C.1 Drive APOGEE FLN Communication Parameter Settings

Parameter Number

HOA Keypad Display

APOGEE FLN Setting

b1-01

Reference Source

2: Serial Com

b1-02

Run Source

2: Serial Com

H1-03

Digital Input Terminal S3 Function Selection

70: Drive Enable2

H5-01

Serial Comm Adr

Select the drive address (default = 1Fh (31 dec))

H5-02

Serial Baud Rate

2: 4800 Baud

H5-08

Protocol Select

2: P1

NOTICE: Damage to Equipment. A Yaskawa representative should set the drive parameters to their appropriate values. Changes made to

the settings of the parameters in

Table C.1

can result in damage to the drive or building equipment.

C.1 APOGEE FLN Set-Up

268