beautypg.com

Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 156

background image

n

T2-06: PM Motor Rated Current

Enter the motor rated current in amps.

No.

Name

Setting Range

Default

T2-06

PM Motor Rated Current

0.0% to 300.0% of the

drive rated current.

Determined by o2-04

n

T2-07: PM Motor Base Frequency

Enter the motor base frequency in Hz.

Note:

T2-07 will be displayed when in OLV/PM.

No.

Name

Setting Range

Default

T2-07

PM Motor Base Frequency

0.0 to 240.0 Hz

87.5 Hz

n

T2-08: Number of PM Motor Poles

Enter the number of motor poles.

No.

Name

Setting Range

Default

T2-08

Number of PM Motor Poles

2 to 48

6

n

T2-10: PM Motor Stator Resistance

Enter the motor stator resistance per motor phase.

No.

Name

Setting Range

Default

T2-10

PM Motor Stator Resistance

0.000 to 65.000 Ω

Determined by T2-02

n

T2-11: PM Motor d-Axis Inductance

Enter the d-Axis inductance per motor phase.

No.

Name

Setting Range

Default

T2-11

PM Motor d-Axis Inductance

0.00 to 600.00 mH

Determined by T2-02

n

T2-12: PM Motor q-Axis Inductance

Enter the q-Axis inductance per motor phase.

No.

Name

Setting Range

Default

T2-12

PM Motor q-Axis Inductance

0.00 to 600.00 mH

Determined by T2-02

n

T2-13: Induced Voltage Constant Unit Selection

Selects the units used for setting the induced voltage coefficient.

No.

Name

Setting Range

Default

T2-13

Induced Voltage Constant Unit Selection

0, 1

0

Setting 0: mV (r/min)

Setting 1: mV (rad/sec)

Note:

If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor Induction

Voltage Constant 1) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.

n

T2-14: PM Motor Induced Voltage Constant (Ke)

Enter the motor induced voltage constant (Ke).

No.

Name

Setting Range

Default

T2-14

PM Motor Induced Voltage Constant

0.0 to 2000.0

Determined by T2-02

1.12 T: Motor Tuning

156

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual