beautypg.com

S5: hoa keypad parameters – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 150

background image

No.

Name

Setting Range

Default

S4-02

BP Energy Save Bypass Trigger Level

0 to 20 Hz

0 Hz

n

S4-03: BP Energy Save Bypass Timer

Sets the time in seconds that the drive should run at the specified speed before entering Energy Save Bypass mode.

No.

Name

Setting Range

Default

S4-03

BP Energy Save Bypass Timer

10 to 60000 s

60 s

n

S4-04: BP Energy Save Bypass Speed Increase

Sets the value in Hz that the drive will increase the output frequency above E1-04 before performing an Energy Save transfer

to bypass.

No.

Name

Setting Range

Default

S4-04

BP Energy Save Bypass Speed Increase

0 to 10 Hz

6 Hz

u

S5: HOA Keypad Parameters

n

S5-01: HAND Frequency Reference Selection

Selects the speed command input source in HAND mode.

No.

Name

Setting Range

Default

S5-01

HAND Frequency Reference Selection

0 to 4

0

Setting 0: HOA Keypad
Setting 1: Terminals
Setting 2: d1-16
Setting 3: S5-05
Setting 4: Determined by b1-01

n

S5-02: HAND/AUTO During Run Selection

Selects if drive will permit switching between HAND and AUTO modes while running.

No.

Name

Setting Range

Default

S5-02

HAND/AUTO During Run Selection

0 or 1

1

Setting 0: Disabled
Setting 1: Enabled

n

S5-03: HAND Mode PI Selection

Selects whether PI control is enabled or disabled when in HAND mode.

No.

Name

Setting Range

Default

S5-03

HAND Mode PI Selection

0 or 1

1

Setting 0: Disabled
Setting 1: Enabled

n

S5-04: HAND Mode Behavior Selection

Selects the behavior of HAND mode.

No.

Name

Setting Range

Default

S5-04

HAND Mode Behavior Selection

0 to 2

1

1.11 S: Special Parameters

150