Setting 0: Legacy Operation Mode

When S5-04 = 0 (Legacy operation mode), the HAND/OFF/AUTO functionality for both the HOA keypad and multifunction

inputs.

Setting 1: Normal Operation Mode

When S5-04 = 1 (Normal operation mode), the functionality is as follows:
• AUTO mode: Drive frequency reference and run command are based on b1-01/b1-02.
• OFF mode: Drive is stopped and cannot run (except via Emergency Override multi-function input). Frequency reference is

based on b1-01.

• HAND mode: Drive runs at frequency reference selected via S5-01.
The AUTO, OFF and HAND states are selected either via the HOA keypad or multi-function inputs.
Parameter S5-01 selects the HAND mode frequency reference source. When S5-01 is set to 2, d1-16 is used as the HAND

mode reference. When S5-01 is set to 3, S5-05 is used. When S5-01 is set to 4, the frequency reference selected via b1-01 is

used as the HAND mode reference.
The only difference between d1-16 and S5-05 is that the unit for d1-16 changes based on o1-03, o1-10 and o1-11. However,

the unit for S5-05 is fixed at Hz.
Parameter S5-03 selects whether PI control is enabled or disabled in HAND mode.

Note:

The drive will always be in AUTO mode at power up with S5-04 = 1.

Table 1.31 HAND/AUTO Multi-Function Inputs, Standard Behavior (S5-04 = 1 or 2)

AUTO Mode Selection

(H1-oo = 6D)

HAND Mode Selection

(H1-oo = 6E)

Operation Mode

Frequency Reference

Run Command

Open

Open

OFF

Based on b1-01

OFF

Open

Closed

HAND

Based on S5-01

OFF

Closed

Open

AUTO

Based on b1-01

Based on b1-02

Closed

Closed

OFF

Based on b1-01

OFF

When the AUTO and HAND multi-function inputs (setting 6D and 6E) are used, the HAND and AUTO keys on the HOA

keypad do not function.
If S5-04 is set to 1 or 2, the AUTO and HAND multi-function inputs (setting 6D and 6E) can only be used together or an

oPE03 error will occur.

AUTO

Fref

via b1-01

Run via b1-02

HAND

Fref via S5-01

Run On

OFF

Fref via b1-01

Run Off

S5-02 = 1 AND

HAND key

S5-02 = 1 AND

AUTO key

OFF key

HAND key

OFF key

AUTO key

Figure 1.82 Standard Behavior (S5-04 = 1 or 2)

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

151

1

Parameter Details